Table 28 — Cooling Service Analysis

PROBLEM

CAUSE

REMEDY

Compressor and

Power failure.

Call power company.

Condenser Fan

 

 

Fuse blown or circuit breaker tripped.

Replace fuse or reset circuit breaker.

Will Not Start.

Defective thermostat, contactor, transformer, or control

Replace component.

 

 

relay.

 

 

Insufficient line voltage.

Determine cause and correct.

 

Incorrect or faulty wiring.

Check wiring diagram and rewire correctly.

 

Thermostat setting too high.

Lower thermostat setting below room temperature.

Compressor Will Not Start

Faulty wiring or loose connections in compressor circuit.

Check wiring and repair or replace.

but Condenser Fan Runs.

 

 

Compressor motor burned out, seized, or internal over-

Determine cause. Replace compressor.

 

 

load open.

 

 

Defective overload.

Determine cause and replace.

 

Compressor locked out

Determine cause for safety trip and reset lockout.

 

One leg of 3-phase power dead.

Replace fuse or reset circuit breaker.

 

 

Determine cause.

Compressor Cycles

Refrigerant overcharge or undercharge.

Recover refrigerant, evacuate system, and recharge

(other than normally

 

to nameplate.

satisfying thermostat).

 

 

Defective compressor.

Replace and determine cause.

 

 

Insufficient line voltage.

Determine cause and correct.

 

Blocked condenser.

Determine cause and correct.

 

Defective overload.

Determine cause and replace.

 

Defective thermostat.

Replace thermostat.

 

Faulty condenser-fan motor.

Replace.

 

Restriction in refrigerant system.

Locate restriction and remove.

Compressor Operates

Dirty air filter.

Replace filter.

continuously.

Unit undersized for load.

Decrease load or increase unit size.

 

 

Thermostat set too low.

Reset thermostat.

 

Low refrigerant charge.

Locate leak, repair, and recharge.

 

Air in system.

Recover refrigerant, evacuate system, and recharge.

 

Condenser coil dirty or restricted.

Clean coil or remove restriction.

Excessive Head Pressure.

Dirty air filter.

Replace filter.

 

Dirty condenser coil.

Clean coil.

 

Refrigerant overcharged.

Recover excess refrigerant.

 

Faulty TXV.

1. Check TXV bulb mounting and secure tightly to

 

 

suction line.

 

 

2. Replace TXV if stuck open or closed.

 

Air in system.

Recover refrigerant, evacuate system, and recharge.

 

Condenser air restricted or air short-cycling.

Determine cause and correct.

Head Pressure Too Low.

Low refrigerant charge.

Check for leaks, repair, and recharge.

 

Restriction in liquid tube.

Remove restriction.

Excessive Suction

High heat load.

Check for source and eliminate.

Pressure.

 

 

Faulty TXV.

1. Check TXV bulb mounting and secure tightly to

 

 

suction line.

 

 

2. Replace TXV if stuck open or closed.

 

Refrigerant overcharged.

Recover excess refrigerant.

Suction Pressure Too

Dirty air filter.

Replace filter.

Low.

Low refrigerant charge.

Check for leaks, repair, and recharge.

 

 

Metering device or low side restricted.

Remove source of restriction.

 

Faulty TXV.

1. Check TXV bulb mounting and secure tightly to

 

 

suction line.

 

 

2. Replace TXV if stuck open or closed.

 

Insufficient evaporator airflow.

Increase air quantity. Check filter and replace if

 

 

necessary.

 

Temperature too low in conditioned area.

Reset thermostat.

 

Field-installed filter drier restricted.

Replace.

LEGEND

TXV — Thermostatic Expansion Valve

45

Page 45
Image 45
Bryant 580F operation manual Cooling Service Analysis

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.