2 LEADS, #18 WIRE 1/32 INSULATION, | REGULATOR |
600V. MAX., 105°C | ADJUSTMENT SCREW |
| (REMOVE COVER) |
OUTLET PRESSURE TAP (PLUGGED)
| RECEPTACLE AND | ||||
ON | TAB COMBINATION | ||||
| C1 | ||||
| TERMINAL | ||||
|
| ||||
OFF |
|
| C2 |
| |
| PILOT ADJ. | PILOT CONNECTION | |||
|
|
| |||
INLET PRESSURE TAP |
|
|
| FOR 1/4” O.D. TUBING | |
|
|
| (PLUGGED) | ||
(PLUGGED) |
|
|
|
| |
1/8 - 27 N.P.T. THDS. | RECEPTACLE TERMINAL |
Fig. 43 — Gas Valve
B.Cleaning and Adjustment
1.Remove burner rack from unit as described in Main Burner Removal section on page 37.
2.Inspect burners, and if dirty, remove burners from rack.
3.Using a soft brush, clean burners and crossover port as required.
4.Adjust spark gap. See Fig. 44.
5.Reinstall burners on rack.
6.Reinstall burner rack as described above.
XI. FILTER DRIER
Replace whenever refrigerant system is exposed to atmosphere.
XII. PROTECTIVE DEVICES
A. Compressor Protection
Overcurrent
Each compressor has internal line break motor protection.
Crankcase Heater
All units are equipped with a
IMPORTANT: After prolonged shutdown or servicing, ener- gize the crankcase heaters for 24 hours before starting the compressors.
Compressor Lockout
If any of the safeties
B. Evaporator Fan Motor Protection
A manual reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or
increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker.
C. Condenser-Fan Motor Protection
Each
D. High and Low-Pressure Switches
If either switch trips, or if the compressor overtemperature switch activates, that refrigerant circuit will be automati- cally locked out by the CLO. To reset, manually move the thermostat setting.
E. Freeze Protection Thermostat (FPT)
An FPT is located on the top and bottom of the evaporator coil. They detect frost
XIII. RELIEF DEVICES
All units have relief devices to protect against damage from excessive pressures (i.e., fire). These devices protect the high and low side.
XIV. CONTROL CIRCUIT, 24-V
This control circuit is protected against overcurrent by a
3.2amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting. See Fig. 45 and 46 for typical wiring diagrams.
XV. REPLACEMENT PARTS
A complete list of replacement parts may be obtained from any Bryant distributor upon request.
XVI. DIAGNOSTIC IGC CONTROL LEDs
The unit control boards have LEDs for diagnostic purposes. Refer to Troubleshooting section on page 43.
XVII. OPTIONAL HINGED ACCESS DOORS
When the optional hinged access doors option is ordered, the unit will be provided with external and internal hinged access doors to facilitate service.
Four external hinged access doors are provided on size 180- 240 units. Two external hinged doors are provided on size 300 units. All external doors are provided with 2 large 1/4 turn latches with folding
Two internal access doors are provided inside the filter/drive access door. The filter access door (on the left) is secured by
2small 1/4 turn latches with folding