CERAMIC
BAFFLE
CLIP
HEAT EXCHANGER
TUBES
NOTE: One baffle and clip will be in each upper tube of the heat exchanger.
Fig. 37 — Removing Heat Exchanger Ceramic
Baffles and Clips
E. Condenser Coil
Clean condenser coil annually and as required by location and
F. Condensate Drain
Check and clean each year at start of cooling season. In winter, keep drains and traps dry.
G. Filters
Clean or replace at start of each heating and cooling season, or more often if operating conditions require. Refer to Table 1 for type and size.
NOTE: The 580F300 unit requires industrial grade throw- away filters capable of withstanding face velocities up to 625 fpm. Ensure that replacement filters for the 580F300 units are rated for 625 fpm.
H. Outdoor-Air Inlet Screens
Clean screens with steam or hot water and a mild detergent. Do not use throwaway filters in place of screens.
II. LUBRICATION
A. Compressors
Each compressor is charged with the correct amount of oil at the factory. Conventional white oil (Sontex 200LT) is used. White oil is compatible with 3GS oil, and 3GS oil may be used if the addition of oil is required. See compressor name- plate for original oil charge. A complete recharge should be four ounces less than the original oil charge. When a compressor is exchanged in the field it is possible that a major portion of the oil from the replaced compressor may still be in the system. While this will not affect the reliability of the replacement compressor, the extra oil will add rotor drag and increase power usage. To remove this excess oil, an access valve may be added to the lower portion of the suction line at the inlet of the compressor. The compressor should then be run for 10 minutes, shut down and the access valve opened until no oil flows. This should be repeated twice to make sure the proper oil level has been achieved.
B. Fan Shaft Bearings
Lubricate bearings at least every 6 months with suitable bearing grease. Extended grease line is provided for far side fan bearing (opposite drive side). Typical lubricants are given below:
MANUFACTURER | LUBRICANT |
Texaco | Regal |
Mobil | Mobilplex EP No. 1 |
Sunoco | Prestige 42 |
Texaco | Multifak 2 |
*Preferred lubricant because it contains rust and oxidation inhibitors.
C. Condenser and Evaporator-Fan Motor Bearings
The condenser and
III.EVAPORATOR FAN PERFORMANCE ADJUSTMENT (Fig. 38 and 39)
Fan motor pulleys are factory set for speed shown in Table 1.
To change fan speeds:
1.Shut off unit power supply.
2.Loosen nuts on the 2 carriage bolts in the motor mounting base. Install jacking bolt and plate under motor base (bolt and plate are shipped in installer’s packet). Using bolt and plate, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts.
3.Loosen
4.Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1.
See Table 21 for air quantity limits.
5.Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)
6.Replace and tighten belts. See Belt Tension Adjust- ment section below.
To align fan and motor pulleys:
1.Loosen fan pulley setscrews.
2.Slide fan pulley along fan shaft.
3.Make angular alignment by loosening motor from mounting plate.
IV. EVAPORATOR FAN SERVICE AND REPLACEMENT
The 580F units use a fan motor mounting system that fea- tures a
1.Remove the
2.Remove the center post (located between the evapora- tor fan and heating control access panels) and all screws securing it.
3.Loosen nuts on the 2 carriage bolts in the motor mounting base.
4.Using jacking bolt under motor base, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts.