Table 1 — Physical Data (cont)
UNIT 580F |
| 180 | 210 | 240 | 300 | ||
| (Low Heat/High Heat) | (Low Heat/High Heat) | (Low Heat/High Heat) | (Low Heat/High Heat) | |||
|
|
|
| ||||
FURNACE SECTION |
|
|
|
|
| ||
Rollout Switch Cutout Temp (F)*** | 190 | 190 | 190 | 190 | |||
Burner Orifice Diameter (in. ...drill size) |
|
|
|
| |||
| Natural Gas | Std | 0.1285...30/0.136...29 | 0.1285...30/0.136...29 | 0.1285...30/0.136...29 | 0.1285...30/0.136...29 | |
Thermostat Heat Anticipator Setting (amps) |
|
|
|
| |||
| 208/230 v | Stage 1 | 0.98 | 0.98 | 0.98 | 0.98 | |
|
|
| Stage 2 | 0.44 | 0.44 | 0.44 | 0.44 |
| 460 v | Stage 1 | 0.80 | 0.80 | 0.80 | 0.80 | |
|
|
| Stage 2 | 0.44 | 0.44 | 0.44 | 0.44 |
| Gas Input | Stage 1 | 206,000/270,000 | 206,000/270,000 | 206,000/270,000 | 206,000/270,000 | |
|
|
| Stage 2 | 275,000/360,000 | 275,000/360,000 | 275,000/360,000 | 275,000/360,000 |
Efficiency | 81 | 81 | 81 | 81 | |||
Temperature Rise Range | |||||||
Manifold Pressure (in. wg) |
|
|
|
| |||
| Natural Gas | Std | 3.3 | 3.3 | 3.3 | 3.3 | |
| Liquid Propane††† | Alt | 3.3 | 3.3 | 3.3 | 3.3 | |
Gas Valve Quantity |
| 1 | 1 | 1 | 1 | ||
Gas Valve Pressure Range |
|
|
|
| |||
| in. wg |
| |||||
| psig |
|
| ||||
Field Gas Connection Size | 3/4 | 3/4 | 3/4 | 3/4 | |||
|
|
|
| ||||
Cutout |
|
|
| 426 |
| ||
Reset (Auto) |
|
| 320 |
| |||
|
|
|
| ||||
Cutout |
|
|
| 27 |
| ||
Reset (Auto) |
|
| 44 |
| |||
FREEZE PROTECTION THERMOSTAT (F) |
|
|
|
| |||
Opens |
|
|
| 30 ± 5 |
| ||
Closes |
|
|
| 45 ± 5 |
| ||
| Cleanable |
| |||||
Quantity...Size (in.) |
|
| 2...20 x 25 x 1 |
| |||
|
|
|
|
| 1...20 x 20 x 1 |
| |
|
| Throwaway¶ |
| ||||
Quantity...Size (in.) |
|
| 4...20 x 20 x 2 |
| |||
|
|
|
|
| 4...16 x 20 x 2 |
| |
POWER EXHAUST |
| 1/2 Hp, | |||||
|
| LEGEND |
|
|
|
| |
Bhp | — | Brake Horsepower |
|
|
|
| |
TXV | — | Thermostatic Expansion Valve |
|
|
|
|
*The ZRU140KC compressor is a tandem compressor, consisting of a ZR72KC (25% total capac- ity) and a ZR68KC (24% total capacity).
†Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils; and Circuit 2 uses the upper portion of both coils.
**Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to 11/2 turns open.
††Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to 1/2 turns open.
***Rollout switch is manual reset.
†††A Liquid Propane kit is available as an accessory.
¶The 580F300 unit requires
NOTE: The 580F units have a