Bryant operation manual Base Unit Dimensions - 580F240

Models: 580F

1 52
Download 52 pages 44.41 Kb
Page 7
Image 7
Fig. 5 — Base Unit Dimensions — 580F240

NOTES:

1.

Refer to print for roof curb accessory dimensions.

2.

Dimensions in [ ] are in millimeters.

3.

 

 

 

 

Center of gravity.

4.

 

 

 

 

 

Direction of airflow.

 

 

 

 

 

 

 

 

 

 

5.

 

 

 

 

to be attached to accessory roof curb only.

Ductwork

6.

Minimum clearance:

 

 

Rear: 7-0(2134) for coil removal. This dimension can be reduced to 4-0

 

 

 

 

(1219) if conditions permit coil removal from the top.

 

 

4-0(1219) to combustible surfaces, all four sides (includes between units).

 

 

Left side: 4-0(1219) for proper condenser coil airflow.

 

 

Front: 4-0(1219) for control box access.

 

 

Right side: 4-0(1219) for proper operation of damper and power exhaust if

 

 

 

 

so equipped.

 

 

Top: 6-0(1829) to assure proper condenser fan operation.

 

 

Bottom: 14(356) to combustible surfaces (when not using curb).

 

 

Control box side: 3-0(914) to ungrounded surfaces, non-combustible.

 

 

Control box side: 3-6(1067) to block or concrete walls, or other grounded

 

 

surfaces.

 

 

Local codes or jurisdiction may prevail.

7.

With the exception of clearance for the condenser coil and the damper/power

 

exhaust as stated in Note #6, a removable fence or barricade requires no clear-

 

ance.

8.

Dimensions are from outside of corner post. Allow 0-5/16(8) on each side for

top cover drip edge.

7

Fig. 5 — Base Unit Dimensions — 580F240

Page 7
Image 7
Bryant operation manual Base Unit Dimensions - 580F240