N1 |
| EXH | TR | TR1 |
N |
| Set |
|
|
2V | 10V |
|
| |
|
|
| ||
P1 | EXH |
| 24 | 24 Vac |
|
| Vac | COM | |
P |
|
| ||
| Min | HOT | _ | |
T1 |
| Pos | + | |
|
| |||
|
|
|
| |
T | Open |
|
| |
|
|
|
| |
|
| DCV | 1 | 2 |
|
| Max | ||
|
|
|
| |
| 2V | 10V |
|
|
AQ1 | DCV |
|
| 5 |
|
|
| ||
|
|
|
| |
AQ |
| DCV |
|
|
SO+ |
| Set | 3 | 4 |
SO | 2V | 10V |
|
|
|
|
|
| |
SR+ | Free |
| EF | EF1 |
| Cool |
|
|
|
SR | B | C |
|
|
| A | D |
|
|
Fig. 32 — EconoMi$erIV Controller
CO2 SENSOR MAX RANGE SETTING
| 6000 |
|
|
|
|
|
|
(ppm) | 5000 |
|
|
|
|
|
|
|
|
|
|
|
|
| |
CONFIGURATION | 4000 |
|
|
|
|
| 800 ppm |
|
|
|
|
|
| ||
3000 |
|
|
|
|
| 900 ppm | |
|
|
|
|
| 1000 ppm | ||
|
|
|
|
|
| ||
2000 |
|
|
|
|
| 1100 ppm | |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
RANGE | 1000 |
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 0 |
|
|
|
|
|
|
| 2 | 3 | 4 | 5 | 6 | 7 | 8 |
| DAMPER VOLTAGE FOR MAX VENTILATION RATE |
Fig. 33 — CO2 Sensor Maximum Range Setting
To determine the minimum position setting, perform the following procedure:
1.Calculate the appropriate
(TO x | OA | ) + (TR x | RA | ) = TM |
100 | 100 |
TO =
As an example, if local codes require 10% outdoor air during occupied conditions,
(60 x .10) + (75 x .90) = 73.5 F
2.Disconnect the
3.Ensure that the
4.Connect 24 vac across terminals TR and TR1.
5.Carefully adjust the minimum position potentiometer until the measured
6.Reconnect the supply air sensor to terminals T and T1.
Remote control of the EconoMi$erIV damper is desirable when requiring additional temporary ventilation. If a
To control the minimum damper position remotely, remove the
Damper Movement
Damper movement from full open to full closed (or vice versa) takes 21/2 minutes.
Thermostats
The EconoMi$erIV control works with conventional thermo- stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$erIV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box.
Occupancy Control
The factory default configuration for the EconoMi$erIV con- trol is occupied mode. Occupied status is provided by the red jumper from terminal
Demand Controlled Ventilation (DCV)
When using the EconoMi$erIV for demand controlled venti- lation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.
A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional- anticipatory strategy will cause the fresh air supplied to increase as the room CO2 level increases even though the CO2 set point has not been reached. By the time the CO2 level reaches the set point, the damper will be at maximum ventilation and should maintain the set point.
In order to have the CO2 sensor control the economizer damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventila- tion required to remove contaminants during unoccupied periods. The following equation may be used to determine the