Bryant 580F operation manual

Models: 580F

1 52
Download 52 pages 44.41 Kb
Page 31
Image 31

Table 18 — Fan Performance — 580F240360 (High Heat Units)*

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,000

868

2752

3.26

934

2987

3.54

997

3227

3.83

1058

3470

4.12

1115

3716

4.41

6,500

929

3201

3.80

991

3436

4.08

1051

3675

4.36

1108

3917

4.65

1162

4163

4.94

7,000

991

3687

4.37

1049

3923

4.65

1105

4161

4.94

1159

4403

5.22

1211

4647

5.51

7,500

1054

4211

5.00

1109

4447

5.28

1161

4686

5.56

1213

4926

5.84

1262

5170

6.13

8,000

1117

4773

5.66

1168

5009

5.94

1218

5247

6.22

1267

5488

6.51

1314

5731

6.80

8,500

1180

5373

6.37

1229

5609

6.65

1277

5847

6.94

1323

6088

7.22

1368

6331

7.51

9,000

1244

6011

7.13

1290

6247

7.41

1335

6485

7.69

1380

6726

7.98

1423

6968

8.27

9,500

1308

6687

7.93

1352

6924

8.21

1395

7162

8.50

1437

7402

8.78

1479

7644

9.07

10,000

1372

7401

8.78

1414

7638

9.06

1455

7876

9.34

1496

8117

9.63

1535

8358

9.92

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,000

1171

3965

4.70

1224

4216

5.00

1276

4469

5.30

1326

4726

5.61

1374

4983

5.91

6,500

1215

4410

5.23

1266

4659

5.53

1316

4911

5.83

1364

5165

6.13

1411

5421

6.43

7,000

1262

4894

5.81

1311

5142

6.10

1358

5392

6.40

1404

5645

6.70

1449

5899

7.00

7,500

1310

5415

6.42

1357

5663

6.72

1403

5912

7.01

1447

6164

7.31

1490

6416

7.61

8,000

1360

5976

7.09

1405

6222

7.38

1449

6471

7.68

1492

6721

7.97

1533

6973

8.27

8,500

1412

6575

7.80

1455

6821

8.09

1497

7068

8.39

1538

7318

8.68

9,000

1465

7212

8.56

1506

7457

8.85

1547

7705

9.14

9,500

1519

7888

9.36

10,000

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

2.2

 

 

2.4

 

 

2.6

 

 

2.8

 

 

3.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,000

1422

5243

6.22

1468

5505

6.53

1513

5768

6.84

6,500

1456

5679

6.74

1501

5938

7.04

1544

6199

7.35

7,000

1493

6155

7.30

1536

6412

7.61

7,500

1533

6670

7.91

8,000

8,500

9,000

9,500

10,000

LEGEND

Bhp — Brake Horsepower

Watts — Input Watts to Motor

*Standard low-medium static drive range is 1002 to 1151 rpm. Alternate high-static drive range is 1193 to 1369. Other rpms require a field- supplied drive.

Refer to page 32 for general Fan Performance Data notes.

NOTE: Maximum continuous bhp for the standard motor is 8.7 (for 208/ 230-v units) and 9.5 (for 460-v units). The maximum continuous watts is 7915 (for 208/230-v units) and 8640 (for 460-v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Table 24 for more information.