Motor Mount — To ensure proper fan height, replace the existing motor mount with the new motor mount provided with accessory.
Transformer
Motormaster® I Control — Recommended mounting location is on the inside of the panel to the left of the control box. The control should be mounted on the inside of the panel, verti- cally, with leads protruding from bottom of extrusion.
B. Motormaster V Control Installation (580F240 and 300)
Install
Wind baffles must be
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.
Install Motormaster V Controls
The Motormaster V control is a motor speed control device which adjusts condenser fan motor speed in response to declining liquid refrigerant pressure. A properly applied Motormaster V control extends the operating range of air- conditioning systems and permits operation at lower outdoor ambient temperatures.
The minimum ambient temperatures at which the unit will operate are:
TEMPERATURE OPERATING LIMITS — F°
Standard | Unit with | Unit with |
Unit | Low Ambient Kit | MMV Control |
40 | 25 |
To operate down to the ambient temperatures listed, Motormaster V controls (Fig. 24) must be added. Field- fabricated and installed wind baffles are also required for all units (see Fig. 22). The Motormaster V control permits opera- tion of the unit to an ambient temperature of
See Table 6 for the Motormaster V control accessory package usage. Table 7 shows applicable voltages and motors. Replacement of motor or fan blade IS NOT REQUIRED ON CURRENT PRODUCTION UNITS since the control is compatible with the
Install the Motormaster V control per instructions supplied with accessory.
Table 6 — Motormaster V Control Package Usage
UNIT | VOLTAGE | ITEM DESCRIPTION | |
208/230 | CRLOWAMB015A00 | ||
|
| ||
460 | CRLOWAMB016A00 | ||
| |||
|
|
|
Table 7 — Applicable Voltages and Motors
VOLTAGE | COMPATIBLE MOTOR |
HD52AK654 | |
HD52AK654 |
NOTE: Dimensions in ( ) are in mm.
Fig. 22 — Wind Baffle Details
SENSOR | SENSOR |
LOCATION | LOCATION |
HAIRPIN END | HAIRPIN END |
580F180580F210
NOTE: All sensors are located on the eighth hairpin up from the bottom.