G. EconoMi$erIV Troubleshooting Completion
This procedure is used to return the EconoMi$erIV to opera- tion. No troubleshooting or testing is done by performing the following procedure.
1.Disconnect power at TR and TR1.
2.Set enthalpy potentiometer to previous setting.
3.Set DCV maximum position potentiometer to previ- ous setting.
4.Set minimum position, DCV set point, and exhaust potentiometers to previous settings.
5.Remove
6.Remove 1.2
7.Remove jumper from TR to N.
8.Remove jumper from TR to 1.
9.Remove 5.6
10.Remove jumper from P to P1. Reconnect device at P and P1.
11.Apply power (24 vac) to terminals TR and TR1.
Table 26 — Perfect Humidity™ Dehumidification Subcooler Service Analysis
PROBLEM | CAUSE |
| REMEDY |
Subcooler Will Not Energize | No power to subcooler control transformer. | Check power source. Ensure all wire connections | |
|
| are tight. | |
| No power from subcooler control transformer to liq- | 1. Fuse open; check fuse. Ensure continuity of wiring. | |
| uid line | 2. | Subcooler control |
|
|
| Cycle unit off and allow |
|
|
| to reset. Replace switch if it will not close. |
|
| 3. | Transformer bad; check transformer. |
| Liquid line | 1. | Solenoid coil defective; replace. |
|
| 2. | Solenoid valve stuck closed; replace. |
Subcooler Will Not Deenergize | Liquid Line | Valve is stuck open; replace. | |
Low System Capacity | Low refrigerant charge or frosted coil. | 1. | Check charge amount. See system charging |
|
|
| section. |
|
| 2. | Evaporator coil frosted; check and replace |
|
|
| subcooler control |
Table 27 — Heating Service Analysis
PROBLEM | CAUSE | REMEDY |
Burners Will Not | Misaligned spark electrodes. | Check flame ignition and sensor electrode positioning. |
Ignite. |
| Adjust as needed. |
| No gas at main burners. | Check gas line for air; purge as necessary. After purging |
|
| gas line of air, allow gas to dissipate for at least 5 minutes |
|
| before attempting to relight unit. |
|
| Check gas valve. |
| Water in gas line. | Drain water and install drip leg to trap water. |
| No power to furnace. | Check power supply, fuses, wiring, and circuit breaker. |
| No 24 v power supply to control circuit. | Check transformer. Transformers with internal overcurrent |
|
| protection require a |
|
| Check |
| Miswired or loose connections. | Check all wiring and wire nut connections. |
| Replace thermostat. | |
| Broken thermostat wires. | Run continuity check. Replace wires if necessary. |
Inadequate Heating. | Dirty air filter. | Clean or replace filter as necessary. |
| Gas input to unit too low. | Check gas pressure at manifold. Clock gas meter for |
|
| input. If too low, increase manifold pressure or replace |
|
| with correct orifices. |
| Unit undersized for application. | Replace with proper unit or add additional unit. |
| Restricted airflow. | Clean filter, replace filter, or remove any restrictions. |
| Blower speed too low. | Install alternate motor, if applicable, or adjust pulley to |
|
| increase fan speed. |
| Limit switch cycles main burners. | Check rotation of blower, thermostat heat anticipator |
|
| settings, and temperature rise of unit. Adjust as needed. |
| Too much outdoor air. | Adjust minimum position. |
|
| Check economizer operation. |
Poor Flame | Incomplete combustion (lack of combustion air) | Check all screws around flue outlets and burner |
Characteristics. | results in: | compartment. Tighten as necessary. |
| Aldehyde odors, CO, sooting flame, or floating flame. | Cracked heat exchanger. |
|
| Overfired unit — reduce input, change orifices, or adjust |
|
| gas line or manifold pressure. |
|
| Check vent for restriction. Clean as necessary. |
|
| Check orifice to burner alignment. |
Burners Will Not Turn | Unit is locked into Heating mode for a one minute | Wait until mandatory one minute time period has |
Off. | minimum. | elapsed or power to unit. |