Bunn System III manual Troubleshooting, Problem, Probable Cause, Remedy

Models: System III

1 40
Download 40 pages 46.35 Kb
Page 7
Image 7

TROUBLESHOOTING

A troubleshooting guide is provided to suggest probable causes and remedies for the most likely problems encountered. If the problem remains after exhausting the troubleshooting steps, contact the Bunn-O-Matic Technical Service Department.

Inspection, testing, and repair of electrical equipment should be performed only by qualified service personnel.

All electronic components have 120 - 240 volt ac and low voltage dc potential on their terminals. Shorting of terminals or the application of external voltages may result in board failure.

Intermittent operation of electronic circuit boards is unlikely. Board failure will normally be permanent. If an intermittent condition is encountered, the cause will likely be a switch contact or a loose connection at a terminal or crimp.

Solenoid removal requires interrupting the water supply to the valve. Damage may result if solenoids are energized for more than ten minutes without a supply of water.

The use of two wrenches is recommended whenever plumbing fittings are tightened or loosened. This will help avoid twists and kinks in the tubing.

Make certain that all plumbing connections are sealed and electrical connections tight and isolated.

This brewer is heated at all times. Keep away from combustibles.

WARNING

Exercise extreme caution when servicing electrical equipment.

Disconnect power source when servicing, except when electrical tests are specified.

Follow recommended service procedures.

Replace all protective shields or safety notices.

Problem

Probable Cause

Remedy

Equipment will not operate.

1. No power or incorrect voltage

(A1) Check the terminal block for

 

 

120 volts across the red and white

 

 

terminals and the black and white

 

 

terminals on 120/208 or 120/240

 

 

volt brewers.

 

 

(A2) Check the terminal block for

 

 

200 volts on "B Series" brewers or

 

 

240 volts on "A Series" brewers

 

 

across the red and black terminals.

 

 

(B) Check circuit breakers or fuses.

Brew cycle will not start.

1. No water

Check plumbing and shut-off valves

 

2. Water strainer/flow control (.500

(A) Direction of flow arrow must be

 

GPM)

pointing towards the right.

 

 

(B) Remove the strainer/flow

 

 

control and check for obstructions.

 

 

Clear or replace.

Page 7

27362

092996

 

 

Page 7
Image 7
Bunn System III manual Troubleshooting, Problem, Probable Cause, Remedy