Table 18 Ð Test of Input Signals

 

 

 

KEYBOARD

DISPLAY

COMMENTS/ACTION

ENTRY

RESPONSE

 

 

INPUTS

Field testing of inputs (X = current value. All temperatures should be 6 2 degrees F from actual)

 

SAT X

Verify that the supply-air temperature sensor reading agrees with the actual temperature.

 

OAT X

Verify that the outdoor-air temperature sensor reading agrees with the actual temperature.

 

SPT X

Verify that the space temperature sensor reading agrees with the actual temperature.

 

RAT X

Verify that the return-air temperature sensor reading agrees with the actual temperature.

 

ENT X

Verify proper enthalpy reading. Move the knob on the enthalpy switch from A to D (or D to A) and verify that

 

the display readout changes.

 

 

 

SFS OFF

Verify that the supply fan status is OFF when the supply fan is OFF.

 

SFS ON

Verify that the supply fan status is ON when the supply fan is ON. (Unit may be started by placing the HOA

 

switch in the HAND position.)

 

 

 

FRZ NRM

Verify that the low limit thermostat reads Normal. If not, reset the low limit thermostat.

 

SP 0.0

Verify that the static pressure reads 0.0 in. wg with the fan OFF and HOA switch set at OFF (VAV units).

 

 

 

Listed below are steps which must be used to verify different options. If the unit is not equipped with MAT, RH, OARH, or FLTS, proceed with the testing of the inputs to the Option Module. If the unit is equipped with any of these options, proceed with their respective testing as follows. If

an option is not present, press for the next available option.

RH XX

MAT X

OARH XX

FLTS NRM

Verify that the relative humidity reading agrees with the actual relative humidity, checked with the local weather bureau.

Verify that the mixed-air temperature sensor reading agrees with the actual temperature.

Verify that the outdoor-air relative humidity reading agrees with the actual relative humidity, checked with the local weather bureau.

Verify that the ®lter status reads Normal.

Listed below are steps which must be used to verify the inputs to the Option Module. If the unit is not equipped with the Option Module, proceed with the testing of the outputs (Table 19). If the unit is equipped with the Option Module, proceed with the testing as follows. If an option

is not present, press for the next available option.

 

TEMP X

Verify that the temperature sensor reading agrees with the actual temperature measured.

 

RVP X

Verify that the return velocity pressure is 0 with the return fan OFF.

 

SVP X

Verify that the supply velocity pressure is 0 with the supply fan OFF.

 

DHH NRM

Verify that the duct high humidity switch reads Normal when the adjustment knob is set to the maximum set

 

point or contacts are open. Verify that it reads ALM when contacts are shorted.

 

 

 

EVAC NRM

At Terminal Block 3, short Terminals 5 and 8. Verify that the display changes to EVAC ALM. Verify the

 

 

following:

 

 

·

Supply fan is OFF

 

 

·

Outside and return dampers (if applicable) close

 

 

·

Exhaust damper (if applicable) opens

 

 

·

Return fan starts

 

 

·

Supply fan inlet guide vanes close (VAV units only)

 

 

·

Return fan inlet guide vanes open (VAV units equipped with return fans)

 

 

·

Heat interlock Relay is OFF (VAV units)

 

PRES NRM

At Terminal Block 3, short Terminals 3 and 8. Verify that the display changes to PRES ALM. Verify the

 

 

following:

 

 

·

Supply fan is ON

 

 

·

Outside air damper (if applicable) opens

 

 

·

Exhaust and return dampers (if applicable) close

 

 

·

Return fan stops

 

 

·

Supply fan inlet guide vanes open (VAV units)

 

 

·

Return fan IGVs close (VAV units equipped with return fan)

 

 

·

Heat Interlock Relay is ON (VAV units)

 

PURG NRM

At Terminal Block 3, short Terminals 4 and 8. Verify that the display changes to PURG ALM. Verify the

 

 

following:

 

 

·

Supply fan is ON

 

 

·

Outside air and exhaust dampers (if applicable) open

 

 

·

Return damper (if applicable) closes

 

 

·

Return fan is ON

 

 

·

Supply fan IGVs open (VAV units)

 

 

·

Return fan IGVs open (VAV units equipped with return fan)

 

 

·

Heat Interlock Relay is ON (VAV units)

104

Page 104
Image 104
Carrier 39L specifications Test of Input Signals, Keyboard Display COMMENTS/ACTION Entry Response

39L specifications

The Carrier 39L is a cutting-edge air conditioning unit designed for both residential and commercial applications, providing exceptional cooling and heating performance. Equipped with advanced technologies, this system ensures optimal climate control while maintaining energy efficiency.

One of the standout features of the Carrier 39L is its inverter technology. This innovation allows the system to adjust its compressor speed based on the ambient temperature, which results in a significant reduction in energy consumption. By operating at varying capacities rather than a fixed output, the 39L can maintain a consistent temperature, enhancing comfort while lowering electricity bills.

The Carrier 39L also includes a high-efficiency air filtration system, designed to capture dust, allergens, and other airborne particles. This not only improves indoor air quality but also promotes a healthier living environment. The filtration system is complemented by anti-bacterial treatment, ensuring that the air circulated within your space is both clean and refreshing.

In terms of design, the Carrier 39L boasts a sleek and compact form factor, making it easy to integrate into various settings, from homes to offices. Its quiet operation is another notable feature, as it minimizes noise levels, allowing occupants to enjoy a serene atmosphere without disruptive sound.

Further enhancing convenience, the Carrier 39L comes equipped with smart connectivity options. Users can control the unit remotely via a smartphone app, making it easy to adjust settings, program schedules, and monitor energy usage from anywhere. This feature not only improves user experience but also supports energy-saving practices.

Durability is also a key characteristic of the Carrier 39L. Constructed with high-quality materials and coated with corrosion-resistant treatments, the unit is built to withstand various environmental conditions. This ensures long-lasting performance and reduces the need for frequent maintenance.

Overall, the Carrier 39L is a versatile, efficient, and user-friendly air conditioning solution. Its blend of advanced technologies, energy-saving capabilities, and robust design makes it an ideal choice for those seeking reliable climate control in their spaces. Whether for residential comfort or commercial necessity, the Carrier 39L stands out as a leader in modern air conditioning.