SMOKE CONTROL Ð When the 39L or 39NX unit is equipped with an optional smoke control and a ®re system is installed, 4 modes are provided to control smoke within areas serviced by the air-handling unit. Each mode must be energized individually from the approved building ®re alarm system, and the corresponding alarm is then generated at the local interface device or Building Supervisor.

The system must include a separate return fan and an ex- haust air damper with a 4 to 20 mA actuator.

The building ®re alarm system must provide 4 normally- open dry contact closures and a double-pole, double-throw (DPDT) relay (24 vac coil, contacts rated 10 amps at 240 vac) for the Fire Shutdown mode.

Fire Shutdown Mode Ð The ®re alarm system must provide a normally-open dry contact closure which, when activated, energizes the Fire Shutdown mode.

When the Fire Shutdown mode is energized, the supply and return fans stop, the outside and exhaust air dampers close, and the return-air dampers open.

This mode remains in effect as long as the input signal is maintained at the ®re system panel. An alarm is generated from this input and sent to the Building Supervisor. In order for this mode to be initiated, the input signal must be main- tained for no less than 2 seconds.

Evacuation Mode Ð The building ®re alarm system must pro- vide a normally-open dry contact closure which, when ac- tivated, energizes the Evacuation mode. When the Evacuation mode is energized, the supply fan shuts down, the return fan starts, the outside-air and return-air dampers close, and the exhaust air dampers open.

This mode remains in effect for as long as the input signal is maintained at the ®re system panel. An alarm is generated from this input and sent to the Building Supervisor. In order for this mode to be initiated, the input signal must be main- tained for no less than 2 seconds.

Pressurization Mode Ð The building ®re alarm system must provide a normally-open dry contact closure which, when activated, energizes the Pressurization mode. When the Pressurization mode is energized, the supply fan starts, the return fan shuts down, the outside dampers open, and the exhaust and return-air dampers close.

This mode remains in effect as long as the input signal is maintained at the ®re system panel. An alarm is generated from this input and sent to the Building Supervisor. In order for this mode to be initiated, the input signal must be main- tained for no less than 2 seconds.

Smoke Purge Mode Ð The building ®re alarm system must provide a normally-open dry contact closure which, when activated, energizes the smoke purge mode.

When the smoke purge mode is energized, the supply fan starts, the return fan starts, the outside air and exhaust air dampers open and the return-air dampers close.

This mode remains in effect as long as the input signal is maintained at the ®re system panel. An alarm is generated from this input and sent to the Building Supervisor. In order for this mode to be initiated, the input signal must be main- tained for no less than 2 seconds.

ADAPTIVE OPTIMAL START Ð Optimal Start is used to heat up or cool down the space prior to occupancy. The pur- pose is to have the space temperature approach and then achieve the occupied set point by time of occupancy. The control uses outdoor-air temperature, space temperature, occupied

set point, and a `K' factor in minutes/degrees to calculate a start time offset, which is the time in minutes that the system should be started in advance of the occupied time. The con- trol monitors its results and adjusts the K factor to assure that the Occupied set point is achieved at time of occupancy.

Constant Volume Units Only

HEATING COIL CONTROL Ð The heating coil control ad- justs the steam or hot water valve. The valve is modulated to prevent the space temperature from falling below the de- sired set point.

If the supply fan is OFF, the heating valve is modulated to maintain a desired minimum duct temperature (fan off value).

If the fan is ON, the system reads the space sensor and computes the supply-air temperature required to satisfy conditions.

Once the required supply-air temperature has been calculated, it is compared to the actual supply-air tempera- ture and the heating coil valve modulates to the required position.

CHILLED WATER COIL COOLING CONTROL Ð The cooling coil control adjusts the chilled water valve. The valve is modulated to prevent space temperature from exceeding the desired set point. The valve holds its normal position if the space temperature is below the set point or the supply fan is OFF.

If the fan is ON, the control reads the humidity sensor (if supplied) and compares the value to the high humidity limit.

If the humidity is higher than the high humidity limit, the chilled water valve fully opens.

If the humidity is below the high humidity limit, the con- trol reads the space temperature sensor and computes the supply- air temperature required to satisfy conditions.

Once the required supply-air temperature has been cal- culated, it is compared to the actual supply-air temperature and the chilled water valve modulates to the position re- quired to maintain desired conditions.

See Fig. 77 for cooling coil operation ¯ow chart.

DIRECT EXPANSION COOLING CONTROL Ð The direct expansion (DX) cooling control regulates the DX cool- ing system. The DX cooling stages are energized and deen- ergized to prevent the space temperature from exceeding the desired set point. The stages remain off if the space tem- perature is below the set point or the supply fan is OFF.

If the supply fan is ON, the control reads the humidity sensor (if supplied) and compares the value to the high humidity limit. If the humidity is higher than the high hu- midity limit, the DX cooling stages are energized to main- tain a minimum supply-air temperature. If the humidity is below the limit, the control reads the space temperature sen- sor and computes the supply-air temperature required to sat- isfy conditions.

Once the required supply-air temperature has been cal- culated, it is compared to the actual supply-air temperature and the required DX cooling stages are energized to main- tain the desired conditions.

See Fig. 77 for cooling operation and Fig. 78 for DX sub- master gain operation. For more complete information, refer to the Application Data book for Product Integrated Con- trols with DX Cooling.

96

Page 96
Image 96
Carrier 39L specifications Constant Volume Units Only

39L specifications

The Carrier 39L is a cutting-edge air conditioning unit designed for both residential and commercial applications, providing exceptional cooling and heating performance. Equipped with advanced technologies, this system ensures optimal climate control while maintaining energy efficiency.

One of the standout features of the Carrier 39L is its inverter technology. This innovation allows the system to adjust its compressor speed based on the ambient temperature, which results in a significant reduction in energy consumption. By operating at varying capacities rather than a fixed output, the 39L can maintain a consistent temperature, enhancing comfort while lowering electricity bills.

The Carrier 39L also includes a high-efficiency air filtration system, designed to capture dust, allergens, and other airborne particles. This not only improves indoor air quality but also promotes a healthier living environment. The filtration system is complemented by anti-bacterial treatment, ensuring that the air circulated within your space is both clean and refreshing.

In terms of design, the Carrier 39L boasts a sleek and compact form factor, making it easy to integrate into various settings, from homes to offices. Its quiet operation is another notable feature, as it minimizes noise levels, allowing occupants to enjoy a serene atmosphere without disruptive sound.

Further enhancing convenience, the Carrier 39L comes equipped with smart connectivity options. Users can control the unit remotely via a smartphone app, making it easy to adjust settings, program schedules, and monitor energy usage from anywhere. This feature not only improves user experience but also supports energy-saving practices.

Durability is also a key characteristic of the Carrier 39L. Constructed with high-quality materials and coated with corrosion-resistant treatments, the unit is built to withstand various environmental conditions. This ensures long-lasting performance and reduces the need for frequent maintenance.

Overall, the Carrier 39L is a versatile, efficient, and user-friendly air conditioning solution. Its blend of advanced technologies, energy-saving capabilities, and robust design makes it an ideal choice for those seeking reliable climate control in their spaces. Whether for residential comfort or commercial necessity, the Carrier 39L stands out as a leader in modern air conditioning.