16
Table 3 — Electrical Data--50HE (cont)
UNIT
SIZE
NOMINAL
V --- P H --- H z
IFM
TYPE
CONV
OUTLET
VOLTAGE
RANGE COMPRESSOR (each) OUTDOOR FAN
IFM
FLA
ELECTRIC HEAT POWER SUPPLY DISCONNECT SIZE
Min Max QTY RLA LRA QTY FLA
CRHEATER
--- --- A 0 0 o r
B00
Actual kW{FLA MCA MOCP** FLA LRA
006
(tons) 4 6 0 --- 3 --- 6 0
STD
NO 414 508 18.4 70.0 10.8 2.6
NONE — — 13.9 20.0 14.0 92.0
006A00 5.5 7.2 13.9 20.0 14.0 92.0
008A00 10.6 13.8 20.5 25.0 19.0 92.0
009A00 12.9 16.8 24.3 25.0 22.0 92.0
008,008 21.1 27.7 37.8 40.0 35.0 92.0
008,009 23.4 30.1 40.8 45 38 92
YES 414 508 18.4 70.0 10.8 2.6
NONE — — 16.6 20.0 16.0 94.0
006A00 5.5 7.2 16.6 20.0 16.0 95.0
008A00 10.6 13.8 23.9 25.0 21.0 95.0
009A00 12.9 16.8 27.7 30.0 25.0 95.0
008,008 21.1 27.7 41.2 45.0 37.0 95.0
008,009 23.4 30.1 44.2 45 40 95
HS
NO 414 508 18.4 70.0 10.8 3.4
NONE — — 14.7 20.0 14.0 101.0
006A00 5.5 7.2 14.7 20.0 14.0 102.0
008A00 10.6 13.8 21.5 25.0 20.0 102.0
009A00 12.9 16.8 25.3 30.0 23.0 102.0
008,008 21.1 27.7 38.8 40.0 36.0 102.0
008,009 23.4 30.1 41.8 45 38 102
YES 414 508 18.4 70.0 10.8 3.4
NONE — — 17.4 20.0 17.0 104.0
006A00 5.5 7.2 17.4 20.0 17.0 104.0
008A00 10.6 13.8 24.9 25.0 22.0 104.0
009A00 12.9 16.8 28.7 30.0 26.0 104.0
008,008 21.1 27.7 42.2 45.0 38.0 104.0
008,009 23.4 30.1 45.2 50 41 104
006
(tons) 5 7 5 --- 3 --- 6 0
STD NO 518 632 17.1 53.0 10.6 2.0 NONE — — 11.5 15 11 65
YES NONE — — 13.6 15 13 67
HS NO 518 632 17.1 53.0 10.6 2.8 NONE — — 12.3 15 12 74
YES NONE — — 14.4 20 14 76
Humidi-
Mi$er
NO 518 632 17.1 53.0 10.8 3.4 NONE — — 12.2 15 12 78
YES NONE — — 14.4 20 14 80
FLA ---Full Load Amps
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
NOTES:
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
{Heater capacity (kW) is based on heater voltage of 240v, 480v or 575v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly
50HE,HJ