FOR OCCUPANCY CONTROL

REPLACE JUMPER WITH

FIELD-SUPPLIED TIME CLOCK

50HE,HJ

LEGEND

Potentiometer Defaults Settings:

NOTES:

DCV— Demand Controlled Ventilation

Power Exhaust

Middle

1.

620 ohm, 1 watt 5% resistor should be removed only when using differential

Minimum Pos.

Fully Closed

 

enthalpy or dry bulb.

IAQ — Indoor Air Quality

 

DCV Max.

Middle

2.

If a separate field-supplied 24 v transformer is used for the IAQ sensor power

LA — Low Ambient Lockout Device

OAT — Outdoor-Air Temperature

DCV Set

Middle

 

supply, it cannot have the secondary of the transformer grounded.

POT — Potentiometer

Enthalpy

C Setting

3.

For field-installed remote minimum position POT, remove black wire jumper

RAT — Return-Air Temperature

 

 

 

between P and P1 and set control minimum position POT to the minimum

 

 

 

 

position.

C06028

Fig. 34 ---EconoMi$er IV Wiring

 

 

 

 

BLACK

4

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

5

 

 

 

 

BLUE

2

 

 

 

 

 

 

500 OHM

 

 

 

8

 

RESISTOR

 

 

 

 

 

VIOLET

 

 

6

NOTE 1

 

 

 

 

 

PINK

 

 

 

 

 

 

 

7

 

RUN

 

 

 

 

 

 

 

 

 

-

 

 

RED

1

NOTE 3

 

 

 

 

+

 

 

 

10

50HJ540573

 

 

 

 

SENSOR 4 - 20 mA

 

YELLOW

 

 

ACTUATOR

 

 

11

ASSEMBLY

OPTIONAL CO2

 

 

 

 

 

 

 

 

 

OUTPUT

 

 

 

9

 

DIRECT DRIVE

 

 

WHITE

12

 

ACTUATOR

 

 

 

ECONOMISER2 PLUG

NOTES:

1.Switch on actuator must be in run position for economizer to operate.

2.PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077 enthalpy sensor.

3.50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

C06029

Fig. 35 ---EconoMi$er2 with 4 to 20 mA Control Wiring

Outdoor Enthalpy Changeover

For enthalpy control, accessory enthalpy sensor (part number HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 27.) When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. The outdoor

enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. The set points are A, B, C, and D. (See Fig. 43.) The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. (See Fig. 27 and 44.)

37

Page 37
Image 37
Carrier 50HJ004, 50HE003-006 installation instructions EconoMi$er IV Wiring