66
C06145
Fig. 64 --- Cooling Charging Chart, 50HJ005 with
Optional Humidi--MiZer Adaptive Dehumidification System
C06146
Fig. 65 --- Cooling Charging Chart, 50HJ007 with
Optional Humidi--MiZer Adaptive Dehumidification System
To Use Cooling Charging Chart, Standard Unit
Take the outdoor ambient temperature and read the suction
pressure gage. Refer to charts to determine what suction
temperature should be. If suction temperature is high, add
refrigerant. If suction temperature is low, carefully recover some
of the charge. Recheck the suction pressure as charge is adjusted.
Example (Fig. 57):
Outdoor Temperature 75°F.........................
Suction Pressure 70 psig...........................
Suction Temperature should be 48°F..................
(Suction temperature may vary ±5°F.)
If a charging device is used, temperature and pressure readings
must be accomplished using the charging charts.
50HE -- 2 TON CHARGING CHART
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
42 52 62 72
SuctionLineTemp(degF)
Suction Line Pressure (psig)
448.0
498.0
548.0
598.0
648.0
698.0
5.5 10.5 15.5 20.5 25.5
Suction Line Temperature (deg C)
Suction Line Pressure (kpa)
FC
125 52
115 4 6
105 41
95 35
85 29
75 24
C06148
Fig. 66 --- Cooling Charging Chart,
Standard 50HE003
50HE -- 3 TON CHARGING CHART
65.0
75.0
85.0
95.0
43 48 53 58 63 68 73 78
SuctionLineTemp(degF)
Suction Line Pressure (psig)
448.2
498.2
548.2
598.2
648.2
6.1 11.1 16.1 21.1
Suction Line Temperature (deg C)
Suction Line Pressure (kpa)
FC
115 4 6
105 41
95 35
85 29
75 24
C06149
Fig. 67 --- Cooling Charging Chart,
Standard 50HE004
50HE -- 4 TON CHARGING CHART
67.0
77.0
87.0
97.0
42 47 52 57 62 67 72 77
SuctionLineTemp(degF)
Suction Line Pressure (psig)
492.0
542.0
592.0
642.0
692.0
5.6 10.6 15.6 20.6 25.6
Suction Line Temperature (deg C)
Suction Line Pressure (kpa)
FC
115 46
105 41
95 35
85 29
75 24
C06150
Fig. 68 --- Cooling Charging Chart,
Standard 50HE005
50HE,HJ