C06142

Fig. 61 ---Cooling Charging Chart,

Standard 50HJ007

C06143

Fig. 62 ---Cooling Charging Chart, 50HJ004 with

Optional Humidi-MiZer Adaptive Dehumidification System

50HE,HJ C06144

Fig. 63 ---Cooling Charging Chart, 50HJ005 with

Optional Humidi-MiZer Adaptive Dehumidification System

NOTE: When using the charging charts, it is important that only the subcooling/reheat dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidification coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed.

The charts reference a liquid pressure (psig) and temperature at a point between the condenser coil and the subcooling/reheat dehumidification coil. A tap is provided on the unit to measure liquid pressure entering the subcooling/reheat dehumidification coil.

IMPORTANT: The subcooling mode charging charts (Fig. 62-65) are to be used ONLY with units having the Humidi-MiZer adaptive dehumidification system. DO NOT use standard charge (Fig. 58-61) for units with Humidi- MiZer system, and DO NOT use Fig. 62-65 for standard units.

65

Page 65
Image 65
Carrier 50HJ004, 50HE003-006 installation instructions Cooling Charging Chart Standard 50HJ007