with a
Compressor restart is accomplished by manual reset at the thermostat by turning the selector switch to OFF position and then to ON position.
Step 10 —Heating
To start unit, turn on main power supply.
Set system selector switch at HEAT position and set thermostat at a setting above room temperature. Set fan at AUTO position.
First stage of thermostat energizes the
If electric heaters do not energize, reset limit switch (located on
TO SHUT OFF UNIT - Set system selector switch at OFF position. Resetting thermostat at a position below room temperature temporarily shuts unit off until space temperature falls below thermostat setting.
Step 11 —Safety Relief
A soft solder joint at the suction line fitting provides pressure relief under abnormal temperature and pressure conditions.
Step 12 —Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuously to provide constant air circulation.
Step 13 —Operating Sequence
Cooling - Units Without Economizer
When thermostat calls for cooling, terminals G and Y1 are energized. The
Heating - Units Without Economizer
When the thermostat calls for heating, terminal W1 will be energized with 24v. The IFC and heater contactor no. 1 (HC1) are energized.
Cooling - Units With Economi$er IV
When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the
Integrated EconoMi$er IV operation on
For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode.
If the increase in cooling capacity causes the
If optional power exhaust is installed, as the
If
because of the increase in fresh air, the
Damper movement from full closed to full open (or vice versa) will take between
If free cooling can be used as determined from the appropriate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply air temperature set point at 50_ to 55_ F.
As the supply air temperature drops below the set point range of 50_ to 55_ F, the control will modulate the
Heating - Units With Economi$er IV
When the room temperature calls for heat, the heating controls are energized as described in the Heating, Units Without Economizer section. When the thermostat is satisfied, the economizer damper moves to the minimum position.
Cooling - Units With Economi$er2, Premierlinkt Control and a Thermostat
When free cooling is not available, the compressors will be controlled by the PremierLink control in response to the Y1 and Y2 inputs from the thermostat.
The PremierLink control will use the following information to determine if free cooling is available:
SIndoor fan has been on for at least 30 seconds.
SThe SPT, SAT, and OAT inputs must have valid readings.
SOAT must be less than 75_F. S OAT must be less than SPT.
SEnthalpy must be LOW (may be jumpered if an enthalpy sensor not available).
SEconomizer position is NOT forced.
When free cooling is available the PremierLink control will control the compressors and economizer to provide a
The 3 routines are based on OAT where: SASP = Supply Air Set Point
DXCTLO = Direct Expansion Cooling Lockout Set Point PID = Proportional Integral
Routine 1 (OAT < DXCTLO)
SY1 energized – economizer maintains a SASP = (SATLO1 + 3).
SY2 energized – economizer maintains a SASP = (SATLO2 + 3).
Routine 2 (DXCTLO < OAT < 68_F)
SIf only Y1 energized, the economizer maintains a SASP = (SATLO1 + 3).
SIf SAT > SASP + 5 and economizer position > 80%, economizer will go to minimum position for 3 minutes or until SAT > 68_F.
SFirst stage of mechanical cooling will be energized. S Integrator resets.
SEconomizer opens again and controls to current SASP after stage one on for 90 seconds.
50HE,HJ
59