SSPT reading is available
S OAT ± SPT
SEconomizer Position is NOT forced
If any of the above conditions are not met, the economizer submaster reference (ECSR) is set to maximum limit and the damper moves to minimum position. The operating sequence is complete. The ECSR is recalculated every 30 seconds.
If an optional power exhaust is installed, as the
If
Heating - Unit With Economi$er2, Premierlink Control and a Room Sensor
Every 40 seconds the controller will calculate the required heat stages (maximum of 3) to maintain
SIndoor fan has been on for at least 30 seconds. S COOL mode is not active.
SOCCUPIED, TEMP. COMPENSATED START or HEAT mode is active.
SSAT reading is available.
SFire shutdown mode is not active.
If all of the above conditions are met, the number of heat stages is calculated; otherwise the required number of heat stages will be set to 0.
If the PremierLink controller determines that heat stages are required, the economizer damper will be moved to minimum position if occupied and closed if unoccupied.
Staging should be as follows: If Heating PID STAGES=2
SHEAT STAGES=1 (50% capacity) will energize HS1 S HEAT STAGES=2 (100% capacity) will energize HS2
If Heating PID STAGES=3 and AUXOUT = HS3
SHEAT STAGES=1 (33% capacity) will energize HS1 S HEAT STAGES=2 (66% capacity) will energize HS2
SHEAT STAGES=3 (100% capacity) will energize HS3
Units With
Dehumidification System
Normal Design Operation
When the rooftop operates under the normal sequence of operation, the compressors will cycle to maintain indoor conditions. (See Fig. 51.)
The
Subcooling Mode
When subcooling mode is initiated, this will energize (close) the liquid line solenoid valve (LLSV) forcing the hot liquid refrigerant to enter into the subcooling coil. (See Fig. 52.)
As the hot liquid refrigerant passes through the subcooling/ reheat dehumidification coil, it is exposed to the cold supply airflow coming through the evaporator coil. The liquid is further
subcooled to a temperature approaching the evaporator
The liquid enters the evaporator coil at a temperature lower than in standard cooling operation. This lower temperature increases the latent capacity of the rooftop unit. The refrigerant passes through the evaporator and is turned into a vapor. The air passing over the evaporator coil will become colder than during normal operation. However, as this same air passes over the subcooling coil, it will be slightly warmed, partially reheating the air.
Subcooling mode operates only when the outside air temperature is warmer than 40_F. A
The scroll compressors are equipped with crankcase heaters to | 50HE,HJ |
| |
provide protection for the compressors due to the additional |
|
refrigerant charge required by the subcooling/reheat coil. |
|
When in subcooling mode, there is a slight decrease in system |
|
total gross capacity (5% less), a lower gross sensible capacity |
|
(20% less), and a greatly increased latent capacity (up to 40% |
|
more). |
|
C06135
Fig. 51 --- Humidi-MiZer Normal
Design Cooling Operation
C06136
Fig. 52 --- Humidi-MiZer Subcooling
Mode Operation
61