N1

 

EXH

TR

TR1

N

 

Set

 

 

2V

10V

 

 

 

 

 

P1

EXH

 

24

24 Vac

 

 

Vac

COM

P

 

 

 

Min

HOT

_

T1

 

Pos

+

 

 

T

Open

 

 

 

 

 

 

 

 

DCV

1

2

 

 

Max

 

 

 

 

 

2V

10V

 

 

AQ1

DCV

 

 

5

 

 

 

 

 

 

 

AQ

 

DCV

 

4

SO+

 

Set

3

SO

2V

10V

 

 

 

 

 

 

SR+

Free

 

EF

EF1

 

Cool

 

 

 

SR

B

C

 

 

 

A

D

 

 

C06038

Fig. 44 ---EconoMi$er IV Control

CO2 SENSOR MAX RANGE SETTING

 

6000

 

 

 

 

 

 

(ppm)

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFIGURATION

4000

 

 

 

 

 

800 ppm

 

 

 

 

 

 

3000

 

 

 

 

 

900 ppm

 

 

 

 

 

1000 ppm

 

 

 

 

 

 

2000

 

 

 

 

 

1100 ppm

 

 

 

 

 

 

 

 

 

 

 

 

 

RANGE

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

2

3

4

5

6

7

8

 

DAMPER VOLTAGE FOR MAX VENTILATION RATE

C06039

Fig. 45 ---CO2 Sensor Maximum Range Setting

CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 8.)

Use setting 1 or 2 for Carrier equipment. (See Table 8.)

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to select the preset number. (See Table 8.)

4.Press Enter to lock in the selection.

5.Press Mode to exit and resume normal operation.

The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

Dehumidification of Fresh Air with DCV Control

Information from ASHRAE indicates that the largest humidity load on any zone is the fresh air introduced. For some applications, a device such as a 62AQ energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most commercial applications.

If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.

Step 7 Adjust Evaporator-Fan Speed

Adjust evaporator-fan speed to meet jobsite conditions.

Tables 9 and 10 show fan rpm at motor pulley settings for the 50HE003-006 and 50HJ004-007 units. Tables 11 and 14 show maximum amp draw of belt-drive motor. Table 13 shows sound data. Refer to Tables 15-34 for performance data. See Table 35 for accessory static pressure drop. See Fig. 47 for the Humidi-MiZersystem static pressure drops.

For units with electric heating, required minimum cfm is 900 for 50HJ004; 1200 for 50HJ005; 1500 for 50HJ006 and 1800 for 50HJ007.

Belt Drive Motors

Fan motor pulleys are factory set for speed shown in Table 1. Check pulley alignment and belt tension prior to start-up.

To change fan speed:

1.Shut off the unit power supply and tag disconnect.

2.Loosen the belt by loosening the fan motor mounting nuts. (See Fig. 47.)

3.Loosen movable pulley flange setscrew (See Fig. 48).

4.Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1.

5.Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)

6.Adjust belt tension and align fan and motor pulleys per guidance below.

NOTE: Once the required flange position is determined for the correct blower rpm, it is recommended (but not required) that the variable pitch pulley be replaced with a corresponding size fixed sheave pulley.

To align fan and motor pulleys:

1.Loosen fan pulley setscrews.

2.Slide fan pulley along fan shaft.

3.Make angular alignment by loosening motor from mount- ing.

To adjust belt tension:

1.Loosen fan motor mounting nuts.

2.Slide motor mounting plate away from fan scroll for

proper belt tension (1/2-in. deflection with 7 to 10 lb of force).

3.Tighten motor mounting nuts.

4.Adjust bolt and tighten nut to secure motor in fixed position.

50HE,HJ

41

Page 41
Image 41
Carrier 50HJ004 Dehumidification of Fresh Air with DCV Control, Adjust Evaporator-Fan Speed, Belt Drive Motors