50HE,HJ
Table
PROBLEM | CAUSE |
| REMEDY |
Subcooling Mode (Liquid Reheat) | No power to control transformer from | Check power source and | |
Will Not Energize. | wire connections are tight. | ||
| No power from control transformer to liquid line | 1. | Fuse open; check fuse. Ensure continuity of wiring. |
| solenoid valve. | 2. | |
|
|
| |
|
|
| not close. |
|
| 3. Transformer bad; check transformer. | |
| Liquid line solenoid valve will not operate. | 1. | Solenoid coil defective; replace. |
|
| 2. | Solenoid valve stuck open; replace. |
| Liquid line solenoid valve will not open. | Valve is stuck closed; replace valve. | |
Low System Capacity. | Low refrigerant charge or frosted evaporator coil. | 1. | Check charge amount. Charge per Fig. |
|
| 2. | Evaporator coil frosted; check and replace |
|
|
| sure switch if necessary. |
Loss of Compressor Superheat | Thermostatic expansion valve (TXV). | 1. | Check TXV bulb mounting, and secure tightly to suc- |
Conditions with Subcooling/Reheat |
| 2. | tion line. |
Dehumidification Coil Energized. |
| Replace TXV if stuck open or closed. |
Table
PROBLEM | CAUSE |
| REMEDY |
Reheat Mode Will Not Energize. | No power to control transformer from | Check power source and | |
| wire connections are tight. | ||
| No power from control transformer to hot gas | 1. | Fuse open; check fuse. Ensure continuity of wiring. |
| line solenoid valve | 2. | |
|
|
| |
|
|
| not close. |
|
| 3. Transformer bad; check transformer. | |
| Hot gas line solenoid valve will not operate. | 1. | Solenoid coil defective; replace. |
|
| 2. | Solenoid valve stuck closed; replace. |
| Low refrigerant charge or frosted evaporator coil. | 1. | Check charge amount. Charge per Fig. |
|
| 2. | Evaporator coil frosted; check and replace |
|
|
| sure switch if necessary. |
Loss of Compressor Superheat | Thermostatic expansion valve (TXV). | 1. | Check TXV bulb mounting, and secure tightly to suc- |
Conditions with Subcooling/Reheat |
| 2. | tion line. |
Dehumidification Coil Energized. |
| Replace TXV if stuck open or closed. | |
Excessive Superheat. | Liquid line solenoid valve will not operate. | Valve is stuck, replace valve. | |
| Hot gas line solenoid valve will not close. | Valve is stuck; replace valve. |
Table 39—EconoMi$er IV Input/Output Logic
|
|
|
|
|
|
|
|
| |
| INPUTS |
|
|
|
|
| OUTPUTS |
| |
Demand Control | Enthalpy* |
|
|
| Compressor | N Terminal† | |||
Outdoor | Return | Y1 | Y2 | Stage | Stage | Occupied | Unoccupied | ||
Ventilation (DCV) | |||||||||
|
| 1 | 2 | Damper | |||||
|
|
|
| ||||||
|
|
|
|
| |||||
Below set | High | Low | On | On | On | On | Minimum position | Closed | |
(DCV LED Off) | (Free Cooling LED Off) |
|
|
|
|
|
|
| |
| On | Off | On | Off |
|
| |||
|
|
| Off | Off | Off | Off |
|
| |
| Low | High | On | On | On | Off | Modulating** (between min. | Modulating** (between | |
| (Free Cooling LED On) |
|
|
|
|
| position and | closed and | |
|
| On | Off | Off | Off | ||||
|
|
| Off | Off | Off | Off | Minimum position | Closed | |
Above set | High | Low | On | On | On | On | Modulating†† (between min. | Modulating†† (between | |
(DCV LED On) | (Free Cooling LED Off) |
|
|
|
|
| position and DCV maximum) | closed and DCV | |
| On | Off | On | Off | |||||
|
|
|
|
|
|
|
| maximum) | |
|
|
| Off | Off | Off | Off |
| ||
| Low | High | On | On | On | Off | Modulating*** | Modulating††† | |
| (Free Cooling LED On) |
|
|
|
|
|
|
| |
|
| On | Off | Off | Off |
|
| ||
|
|
| Off | Off | Off | Off |
|
|
*For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied). **Modulation is based on the
††Modulation is based on the DCV signal.
***Modulation is based on the greater of DCV and
†††Modulation is based on the greater of DCV and