50HE,HJ

Table 37—Humidi-MiZerAdaptive Dehumidification System Subcooling Mode Service Analysis

PROBLEM

CAUSE

 

REMEDY

Subcooling Mode (Liquid Reheat)

No power to control transformer from

Check power source and evaporator-fan relay. Ensure all

Will Not Energize.

evaporator-fan motor.

wire connections are tight.

 

No power from control transformer to liquid line

1.

Fuse open; check fuse. Ensure continuity of wiring.

 

solenoid valve.

2.

Low-pressure switch open. Cycle unit off and allow

 

 

 

low-pressure switch to reset. Replace switch if it will

 

 

 

not close.

 

 

3. Transformer bad; check transformer.

 

Liquid line solenoid valve will not operate.

1.

Solenoid coil defective; replace.

 

 

2.

Solenoid valve stuck open; replace.

 

Liquid line solenoid valve will not open.

Valve is stuck closed; replace valve.

Low System Capacity.

Low refrigerant charge or frosted evaporator coil.

1.

Check charge amount. Charge per Fig. 59-62.

 

 

2.

Evaporator coil frosted; check and replace low-pres-

 

 

 

sure switch if necessary.

Loss of Compressor Superheat

Thermostatic expansion valve (TXV).

1.

Check TXV bulb mounting, and secure tightly to suc-

Conditions with Subcooling/Reheat

 

2.

tion line.

Dehumidification Coil Energized.

 

Replace TXV if stuck open or closed.

Table 38—Humidi-MiZerAdaptive Dehumidification System Hot Gas Reheat Mode Service Analysis

PROBLEM

CAUSE

 

REMEDY

Reheat Mode Will Not Energize.

No power to control transformer from

Check power source and evaporator-fan relay. Ensure all

 

evaporator-fan motor.

wire connections are tight.

 

No power from control transformer to hot gas

1.

Fuse open; check fuse. Ensure continuity of wiring.

 

line solenoid valve

2.

Low-pressure switch open. Cycle unit off and allow

 

 

 

low-pressure switch to reset. Replace switch if it will

 

 

 

not close.

 

 

3. Transformer bad; check transformer.

 

Hot gas line solenoid valve will not operate.

1.

Solenoid coil defective; replace.

 

 

2.

Solenoid valve stuck closed; replace.

 

Low refrigerant charge or frosted evaporator coil.

1.

Check charge amount. Charge per Fig. 59-62.

 

 

2.

Evaporator coil frosted; check and replace low-pres-

 

 

 

sure switch if necessary.

Loss of Compressor Superheat

Thermostatic expansion valve (TXV).

1.

Check TXV bulb mounting, and secure tightly to suc-

Conditions with Subcooling/Reheat

 

2.

tion line.

Dehumidification Coil Energized.

 

Replace TXV if stuck open or closed.

Excessive Superheat.

Liquid line solenoid valve will not operate.

Valve is stuck, replace valve.

 

Hot gas line solenoid valve will not close.

Valve is stuck; replace valve.

Table 39—EconoMi$er IV Input/Output Logic

 

 

 

 

 

 

 

 

 

 

INPUTS

 

 

 

 

 

OUTPUTS

 

Demand Control

Enthalpy*

 

 

 

Compressor

N Terminal†

Outdoor

Return

Y1

Y2

Stage

Stage

Occupied

Unoccupied

Ventilation (DCV)

 

 

1

2

Damper

 

 

 

 

 

 

 

 

 

Below set

High

Low

On

On

On

On

Minimum position

Closed

(DCV LED Off)

(Free Cooling LED Off)

 

 

 

 

 

 

 

 

On

Off

On

Off

 

 

 

 

 

Off

Off

Off

Off

 

 

 

Low

High

On

On

On

Off

Modulating** (between min.

Modulating** (between

 

(Free Cooling LED On)

 

 

 

 

 

position and full-open)

closed and full-open)

 

 

On

Off

Off

Off

 

 

 

Off

Off

Off

Off

Minimum position

Closed

Above set

High

Low

On

On

On

On

Modulating†† (between min.

Modulating†† (between

(DCV LED On)

(Free Cooling LED Off)

 

 

 

 

 

position and DCV maximum)

closed and DCV

 

On

Off

On

Off

 

 

 

 

 

 

 

 

maximum)

 

 

 

Off

Off

Off

Off

 

 

Low

High

On

On

On

Off

Modulating***

Modulating†††

 

(Free Cooling LED On)

 

 

 

 

 

 

 

 

 

On

Off

Off

Off

 

 

 

 

 

Off

Off

Off

Off

 

 

*For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.

†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied). **Modulation is based on the supply-air sensor signal.

††Modulation is based on the DCV signal.

***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (sup- ply-air signal).

†††Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-air sig- nal).

70

Page 70
Image 70
Carrier 50HE003-006, 50HJ004 installation instructions EconoMi$er IV Input/Output Logic, Subcooling Mode Liquid Reheat