Table 9—50HJ and 50he Fan Rpm at Motor Pulley Setting With Standard Motor*

UNIT

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

50HJ

 

 

 

 

 

 

 

 

 

 

 

 

 

50HE

0

1/2

1

11/2

2

21/2

3

31/2

4

41/2

5

51/2

6

003

936

906

876

846

816

786

756

726

696

666

639

004

1044

1008

971

935

898

862

826

789

753

716

680

005

1185

1144

1102

1061

1019

978

936

895

853

812

770

006

1460

1425

1389

1354

1318

1283

1248

1212

1177

1141

1106

1070

1035

007

1585

1538

1492

1445

1399

1352

1305

1259

1212

1166

1119

*Approximate fan rpm shown (standard motor/drive).

Table 10—50HJ, 50HE Fan Rpm at Motor Pulley Setting With High-Static Motor*

UNIT

 

 

 

 

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

 

 

 

 

0

 

1/

 

1

 

11/

 

2

 

 

21/

 

3

 

31/

 

 

4

 

41/

 

5

 

51/

 

6

 

 

 

 

 

 

 

 

 

 

 

 

004

 

 

2

 

 

 

2

 

 

 

 

2

 

 

 

2

 

 

 

 

2

 

 

 

2

 

 

1455

 

1423

 

1392

 

1360

 

1328

 

 

1297

 

1265

 

1233

 

 

1202

 

1170

 

1138

 

1107

 

1075

005

1455

 

1423

 

1392

 

1360

 

1328

 

 

1297

 

1265

 

1233

 

 

1202

 

1170

 

1138

 

1107

 

1075

006

1685

 

1589

 

1557

 

1525

 

1493

 

 

1460

 

1428

 

1396

 

 

1364

 

1332

 

1300

 

 

007

1685

 

1589

 

1557

 

1525

 

1493

 

 

1460

 

1428

 

1396

 

 

1364

 

1332

 

1300

 

 

*Approximate fan rpm shown (high-static motor/drive).

Table 11—Evaporator-Fan Motor Data — Standard Motor

UNIT

UNIT

MAXIMUM

MAXIMUM

 

MAXIMUM

50HJ

UNIT VOLTAGE

PHASE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

50HE

 

 

 

 

 

 

003

ALL

0.58

580

2.0

75.0

 

Single

1.20

1000

208/230

4.9

004

 

 

 

208/230

4.9

Three

1.20

1000

460

2.2

 

 

Single

1.20

1000

575

2.2

 

208/230

4.9

005

 

 

 

208/230

4.9

Three

1.20

1000

460

2.2

 

 

Single

1.30

1650

575

2.2

 

208/230

9.2

006

 

 

 

208/230

6.7

Three

2.40

2120

460

3.0

 

 

 

 

 

575

3.0

007

Three

2.40

2120

208/230

6.7

460

3.0

 

 

 

 

575

3.0

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

Table 12—Evaporator-Fan Motor Data — High-Static Motors

UNIT

 

UNIT

 

MAXIMUM

 

MAXIMUM

 

MAXIMUM

 

 

 

 

50HJ

 

 

 

UNIT VOLTAGE

 

PHASE

 

CONTINUOUS BHP*

 

OPERATING WATTS*

AMP DRAW

50HE

 

 

 

 

 

 

 

 

 

 

208/230

6.7

004

 

Three

 

2.40

 

2120

 

 

 

460

3.0

 

 

 

 

 

 

 

575

3.0

005

 

Three

 

2.40

 

2120

208/230

6.7

 

 

 

460

3.0

 

 

 

 

 

 

 

575

3.0

006

 

Three

 

2.90

 

2615

208/230

8.6

 

 

 

460

3.9

 

 

 

 

 

 

 

575

3.9

007

 

Three

 

2.90

 

2615

208/230

8.6

 

 

 

460

3.9

 

 

 

 

 

 

 

575

3.9

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.