Table 5—PremierLinkSensor Usage

APPLICATION

OUTDOOR AIR

RETURN AIR

OUTDOOR AIR

RETURN AIR

TEMPERATURE SENSOR

TEMPERATURE SENSOR

ENTHALPY SENSOR

ENTHALPY SENSOR

 

 

 

 

 

 

Dry Bulb

 

 

 

 

Temperature with

Included ---

 

 

 

PremierLink*

(PremierLink

CRTEMPSN001A00

requires 4-20 mA

 

 

 

 

Actuator)

 

 

 

 

Differential Dry Bulb

 

 

 

 

Temperature with

Included ---

Required ---

 

 

PremierLink*

 

 

33ZCT55SPT

(PremierLink

CRTEMPSN001A00

or Equivalent

 

 

requires 4-20 mA

 

 

 

 

 

 

 

Actuator)

 

 

 

 

Single Enthalpy with

 

 

Required ---

 

PremierLink*

Included ---

 

 

(PremierLink

HH57AC077

Not Used

requires 4-20 mA

 

or Equivalent

 

 

 

 

Actuator)

 

 

 

 

 

 

 

 

 

Differential Enthalpy

 

 

Required ---

Required ---

with PremierLink*

Included ---

 

(PremierLink

HH57AC077

HH57AC078

Not Used

requires 4-20 mA

 

or Equivalent

or Equivalent

 

 

Actuator)

 

 

 

 

 

 

 

 

 

*PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature sensor CRTEMPSN001A00

Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.

NOTES:

1. CO2 Sensors (Optional):

33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 — Aspirator box used for duct-mounted CO2 room sensor.

33ZCT55CO2 — Space temperature and CO2 room sensor with override. 33ZCT56CO2 — Space temperature and CO2 room sensor with override and set point.

2. All units include the following Standard Sensors:

Outdoor-Air Sensor — 50HJ540569 — Opens at 67_F, closes at 52_F, not adjustable.

Mixed-Air Sensor — HH97AZ001 — (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature Sensor CRTEMPSN001A00)

Compressor Lockout Sensor — 50HJ540570 — Opens at 35_F, closes at 50_F.

C06016

Fig. 22 ---PremierLink Controller

32

Page 32
Image 32