Table 11 – Speed Selection
COLOR | SPEED | AS SHIPPED |
Gray | 5 | COOL |
Yellow | 4 | SPARE |
Blue | 3 | HEAT |
Orange | 2 | SPARE |
Red | 1* | CONT FAN |
*
!CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the rating plate. Recommended operation is at the
6.Set thermostat heat anticipator.
a.Mechanical thermostat - Set thermostat heat anticipator to match the amp. draw of the electrical components in the
(2.) Connect an amp. meter as shown in Fig. 54 across the R and W subbase terminals or R and W wires at wall.
(3.) Record amp. draw across terminals when furnace is in heating and after blower starts.
(4.) Set heat anticipator on thermostat per thermostat instructions and install on subbase or wall.
b. Electronic thermostat: Set cycle rate for 4 cycles per hr.
7.Adjust blower off delay The blower off delay has 4 adjustable settings from 90 sec to 180 sec. The blower off delay jumpers are located on the furnace control board. (See Fig. 24.)
To change the blower off delay setting, move the jumper from one set of pins on the control to the pins used for the selected blower off delay. Factory off delay setting is 120 sec.
8.Set airflow CFM for cooling
Select the desired blower motor speed lead for cooling airflow. See Table
Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the
1.Check Main Limit Switch(es)
This control shuts off combustion control system and energizes
a.Run furnace for at least 5 minutes.
b.Gradually block off return air with a piece of cardboard or sheet metal until the limit trips.
c.Unblock return air to permit normal circulation.
d.Burners will
2.Check draft safeguard switch.
The purpose of this control is to cause the safe shutdown of the furnace during certain blocked vent conditions.
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
R Y W G
10 TURNS
FROM UNIT
CONTROL TERMINALS
EXAMPLE: | 5.0 AMPS ON AMMETER | = | 0.5 AMPS FOR THERMOSTAT | |
10 TURNS AROUND JAWS | ANTICIPATOR SETTING | |||
|
|
A96316
Fig. 54 - Amp. Draw Check with Ammeter
a.Verify vent pipe is cool to the touch.
b.Disconnect power to furnace and remove vent connector from furnace vent elbow.
c.Restore power to furnace and set room thermostat above room temperature.
d.After normal
e.Furnace should cycle off within 2 minutes. If gas does not shut off within 2 minutes, determine reason draft safeguard switch did not function properly and correct condition.
f.Remove blockage from furnace vent elbow.
g.Switch will
h.
NOTE: Should switch remain open longer than 3 minutes, furnace control board will lockout the furnace for 3 hours. To reset furnace control board, turn thermostat below room temperature or from HEAT to OFF and turn 115v power OFF, then back ON.
3.Check Pressure Switch
This control proves operation of the draft inducer blower.
a.Turn off
b.Disconnect inducer motor lead wires from wire harness.
c.Turn on
d.Set thermostat to “call for heat” and wait 1 minute. When pressure switch is functioning properly, hot surface igniter should NOT glow and control diagnostic light flashes a status code 32. If hot surface igniter glows when inducer motor is disconnected, shut down furnace immediately.
e.Determine reason pressure switch did not function properly and correct condition.
f.Turn off
g.Reconnect inducer motor wires, replace outer door, and turn on
h.Blower will run for 90 sec before beginning the call forheat again.
i.Furnace should ignite normally.
58PHA
39