58PHA
45 CONTROLCIRCUITRYLOCKOUT | Replacefurnacecontrol. | Checkforcontinuityintheharnessandigniter. Replacedefectivecomponent. |
| NO | YES |
| Unplugigniterharnessfromcontrolandinitiate anothercomponenttestsequence.Check |
Checkconnections.IfOK,replacecontrol. | Checkthatallgasvalvesareturnedon. Replacevalve. |
|
NO |
|
|
ReconnecttheRthermostatleadandset thermostattocallforheat.Connectvoltmeter | acrossgasvalveconnections.Doesgasvalve receive24V? | YES |
Checkfor: | - Inadequateflamecarryoverorrough ignition. - Lowinletgaspressure. - Properfiringrate. - | Allowblowertocomeonandrepeattestto checkforintermittentoperation. |
| Checkconnectionsandretry.Ifcurrentis | burnerswillnotstayon,replacecontrol. |
|
| Replaceelectrode. |
| Replacefurnacecontrol. |
|
| |||
NO |
| NO |
| YES |
| NO |
|
|
| NO |
| NO |
|
| |
Doesgasvalveopenandallowgastoflow? | YES | Dothemainburnersignite? | YES | Dothemainburnersstayon? | NO | Repeatcallforheatandcheckflamesensor | currentduringtrialforignitionperiod.Isthe | DCmicroampsbelow0.5? | YES | Cleanflamesensorwithfinesteelwooland recheckcurrent.Nominalcurrentis4.0to6.0 microamps. | Iscurrentneartypicalvalue? | YES | Willmainburnersigniteandstayon? | YES | Fixed. |
NO | YES |
Adapter Kit
31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED – If open longer than 5 minutes, inducer shuts off for 15 minutes before retry. If opens during blower on- delay period, blower will come on for the selected blower
11 NO PREVIOUS CODE – Stored codes are erased after 72 hours. On RED LED boards stored status codes can also be erased whenever power (115V or 24V) is interrupted. Run system through a heating or cooling cycle to check system.
Lowinducervoltage(115V). Lowinletgaspressure(ifLGPSused). Inadequatecombustionairsupply. Disconnectedorobstructedpressure tubing. | Defectiveinducermotor. Defectivepressureswitch. Excessivewind. Restrictedvent. |
- - - - | - - - - |
12 BLOWER ON AFTER POWER UP – (115V OR 24V) – Normal operation. Blower runs for 90 seconds, if unit is powered up during a call for heat
33 LIMIT CIRCUIT FAULT – Indicates the limit, draft safeguard, flame rollout, or blocked vent shutoff switch* (if used) is open. Blower will run for 4 minutes or until open switch remakes whichever is
13 LIMIT CIRCUIT LOCKOUT – Lockout occurs if the limit, draft safeguard, flame rollout, or blocked vent switch*(if used) is open longer than 3 minutes. Control will
longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 min. status code #33 continues to flash until blower shuts off. Flame rollout switch and BVSS requires manual reset. Check for:
14 IGNITION LOCKOUT – System failed to ignite gas and prove flame in 4 attempts. Control will
- Dirtyfilterorrestrictedductsystem. - Looseblowerwheel. - Defectiveswitchorconnections. - Defectiveblowermotororcapacitor. - Inadequatecombustionairsupply (flamerolloutswitchopen). - Restrictedvent. - Properventsizing. - Excessivewind. | |
| 34 |
PRESSURESWITCHDIDNOTOPEN Checkfor: - Obstructedpressuretube. - Pressureswitchstuckclosed. | ||
21 | 22 | 23 |
- Gas valve turned off. - Manual
24 SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24V) wiring including thermostat leads. Disconnect thermostat leads to isolate short circuit.
* Blocked vent shutoff switch used in Chimney
A05032
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 | Printed in U.S.A. | Edition Date: 11/08 | Catalog No: |
|
| ||
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. | Replaces: |
54