Chromalox CN2110 manual Adjusting Set Point and Configuration, Adjusting the Set Point

Models: CN2110

1 32
Download 32 pages 49.67 Kb
Page 16
Image 16

Omega

Section 4—Adjusting Set Point and Configuration

Adjusting the Set Point

1.Set selection switches (see Figure 3.1).

2.Apply power to the unit.

3.To adjust the set point on the CN 2110 Temperature Controller, press and hold the Set Point button (see Figure 4.1). The Set Point light is illuminated and the set point value is displayed.

4.While still pressing the Set Point button, press either theorbutton to adjust the set point to the desired value (see Figure 4.2).

5.Release the Set Point button.

Load

°F

Alarm

°C

Load

°F

Alarm

°C

Temp Set PointTemp Set Point

Set

Set

Point

Point

 

Figure 4.1

Figure 4.2

 

Establishing the Set Point

Adjusting the Set Point

Configuration

While the CN 2110 default settings make it a simple setup controller for

 

most applications, additional programmable menus can be configured

through three front-panel pushbuttons.

To access the user configuration menus,

1.Press and hold theandbuttons. After three seconds the display will begin to toggle between the current security code and LocH (LOCK). The Temp and Set Point LEDs will turn on. See Figure 4.3.

2.Press theorbutton to adjust the value to the appropriate security number (see Security Codes and Levels). Only the value is displayed during adjustment. See Figure 4.4.

3.Press and hold the Set Point () button and press theor buttons to scroll the configuration menus. The display will show the name of the menu and then begin to toggle between the name and the current value. See Figures 4.5 and 4.6.

CN 2110

12

Section 4–Adjusting Set Point and Configuration

Page 16
Image 16
Chromalox CN2110 manual Adjusting Set Point and Configuration, Adjusting the Set Point