CN 2110 Temperature Controller

Section 6—Replacing Output Modules

Module Option Descriptions

The CN 2110 Temperature Controller was shipped with the output modules installed as ordered. The 10A Solid State Relay and 20A Mechanical Relay output cards control small cartridge heater or strip heater loads directly, eliminating the need for a remote contactor or solid state relay. If a larger load is required, the CN 2110 can be configured with a 1A Pilot Duty Relay or Solid State Relay Drive.

The CN 2110 may be optionally configured with a 5A/120V Alarm Relay. Alternate modules, configured with or without alarm, can be installed as needs change.

Control and alarm outputs can be changed in the field.

Output Module options are as follows

 

 

Factory

 

 

 

Load/Sourcing

Default

Part No

Part No.

Description

Specification

Cycle Time

w/o Alarm

w/ Alarm

 

 

 

 

 

R1 Relay

Form A contact, SPST,

30 sec.

2110X-R1

2110X-R1-AL

 

N.O. 1.0 Amp at 120/240

 

 

 

 

VAC resistive load

 

 

 

R20 Relay

Form A contact, SPST,

30 sec.

2110X-R20

2110X-R20-AL

 

N.O. 20 Amp at 240 VAC,

 

 

 

 

28 VDC resistive load

 

 

 

DC SSR Drive

24 VDC nominal at 40

1 sec.

2110X-DC

2110X-DC-AL

 

mA

 

 

 

T1 TRIAC

1 amp continuous, 10

1 sec.

2110X-T1

2110X-T1-AL

 

Amp in-rush 120/240 VAC

 

 

 

T5 Solid State

120/240 VAC, 5 Amp @

1 sec.

2110X-T5

2110X-T5-AL

Power

40°C ambient

 

 

 

Controller

 

 

 

 

T10 Solid State

120/240 VAC, 10 Amp @

1 sec.

 

 

Power

40°C ambient with built-

 

2110X-T10

2110X-T10-AL

Controller

in cooling fan mounted

 

 

(Fan Kit)

(Fan Kit)

 

on rear of housing

 

 

 

 

 

Module Installation

!

WARNING: Remove power from the controller before changing the output module. Failure to do so could cause damage to controller and/or personal injury or death from electrical shock.

When handling output modules, be careful to guard the module against static discharge. Follow the steps below to remove an existing output module and replace it with a new module.

Removal

1.

Remove power from the controller.

 

2.

Remove all terminal connections.

continued

 

 

Section 6–Replacing Output Modules

17

CN 2110

Page 21
Image 21
Chromalox CN2110 manual Replacing Output Modules, Module Option Descriptions, Module Installation, Removal