Omega

Security Codes and Levels

To limit access to the user configuration interface, security codes are assigned to different menu levels. Make security codes available to operators, maintenance crew, supervisors, etc. according to what func- tion level you want for each group. Security Level C is not recom- mended for most users. Gain access to configuration menus using the following codes.

Security Level

Security Code

Function

 

 

 

A

All Values

Allows adjustment of

 

 

the Set Point

B

458

Basic menus

C

736

Calibration menus

Configuration Menus

The following configuration menus can be accessed through the user interface (see Configuration, page 12).

Menu

Adjustable

Factory

Security

Code Function

Range

Default

Level

 

 

 

 

Security Lock

0-999

458

A

Process Variable Display

Read Only

N/A

A

Displays the actual process

°

°

 

 

temperature.

F or

C

 

 

 

 

 

 

Process Set Point Adjust

Sensor Range

0°F

A

Adjusts the target process

°

°

 

 

 

F or

C

 

 

temperature.

Proportional Band

Temperature range above/below set point where proportional control is active. Most applications require a band between 10 to 200°F. This menu is active only when the dip switch is set to “PI”

1 to Sensor 25 B Span Maximum

°F or °C

Automatic Reset

0.0 to 100.0

0.1

B

Control feature that

Repeats/Min.

 

 

automatically corrects for small temperature offsets that occur in proportional control. The higher the setting, the faster the correction occurs. A high setting could cause overshoot during start-up. A low setting will not allow process temperature to reach to set point quickly enough. A setting of “0” turns off automatic reset. This menu is active only when the dip switch is set to “PI”.

CN 2110

14

Section 4–Adjusting Set Point and Configuration

Page 18
Image 18
Chromalox CN2110 manual Security Codes and Levels, Configuration Menus