Approved Scenarios and Scenarios Not Approved for Dual DC Power Supply Configuration

You can connect a single DC power source to either the A input or the B input. If there are dual power sources, connect one source to the A input and one source to the B input. Both sources must be the same polarity (with respect to ground) and voltage (within 0.25 volts). Do not connect –DC grounded and +DC grounded dual sources to Cisco 2811, Cisco 2821, and

Cisco 2851 series integrated services routers.

Caution Dual sources with opposite-polarity grounding damage equipment.

In Figure 21, either the positive source terminal or the negative source terminal is tied to ground.

Figure 21 Connecting to One Source Only—Source A or Source B

+

A-

A+

B+

B-

+

A-

A+

B+

B-

127037

In Figure 22, source A and source B share common negative terminal connections.

Figure 22 Connecting Source A and Source B with Common Negative Terminals

Va

+

+

Vb

A-

A+

B+

B-

127039

In Figure 23, source A and source B share common positive terminal connections. This is allowed only if Va equals Vb (within 0.25 V).

Caution When connecting source A and source B with common positive terminals, if source A and source B voltages are unequal by more than 0.25 V, the higher-voltage source can discharge into the lower-voltage source through the A- and B- input terminals. Excessive discharging currents through these terminals can cause one or both of the dual input DC power supply's internal A- or B- fuses to open, resulting in lack of redundancy or system failure. When source A and source B are within 0.25 V, discharge current is minimal.

24

Page 24
Image 24
Cisco Systems 2800 manual Connecting to One Source Only-Source a or Source B