2.Water supply to the product is correct and flow over the evaporator is correct.
3.Cuber refrigerant charge is correct.
4.TXV sensing bulb is properly located and secured to the suction line and correctly insulated.
5.Hot gas valve(s) are not leaking and/or seeping through.
Starving TXV - Product Symptoms
1.Suction pressure lower than normal for the operating conditions.
2.Ice production lower than normal and/or none.
3.Ice pattern on evaporator (if any) thin at top and thick at bottom.
Flooding TXV - Product Symptoms
1.Ice production lower than normal and/or none.
2.Suction pressure stabilizes at higher than normal pressure for operating conditions. Suction pressure does not modulate and may start to slowly rise.
3.Ice pattern will be very heavy at the bottom and thin at the top of the evaporator. Product may not enter harvest cycle because of higher than normal suction line temperature.
IMPORTANT: Frost on the suction line may be normal on medium temperature refrigeration equipment. Frost should be considered a red flag, long run times will normally produce some type of frost pattern. Before checking the sealed refrigeration system, the external conditions that could lead to frost follow:
1.Dirty condenser
2.Dirty condenser fan blade
3.Improper air clearance around Cuber
4.Loose TXV bulb mount
5.Poor water flow over evaporator
6.Ventilation problems
The expansion valves used on Cornelius “I” series ice equipment have special super heat settings and bulb charge designed for the product load and HP 62 refrigerant. Should the need arise to replace this or any refrig- erant components, be certain to use only components recommended by Cornelius for the model of the Cuber being serviced. Use of nonapproved components will compound system difficulties and may void product war- ranty.
WATER REGULATING VALVE
The water regulating valve is used on
Should adjustment be required, the valve has an adjustment stem on the top of the valve. After allowing the cuber to operate for 10 minutes in the ice– making mode to balance the system, turning the adjusting stem CW will increase the discharge water temperature, and CCW will decrease the discharge water temperature.
The water regulating valve must close off condenser water flow completely during the “hot gas” harvest cycle. There should be no discharge water flowing out of the condenser during the harvest cycle. Should the valve fail to close during the harvest mode, the condenser will continue to condense the compressor discharge vapor needed for the harvest cycle and this will result in long harvest times.
Also discharge water temperature below 108_F /112_F will result in long harvest times.
Leaking (bypassing) water regulating valves are normally the result of scale
Damage to the water regulating valve may also be caused by water hammer. Water hammer will result from the condenser inlet and outlet water lines being reversed or defective valve stops in the water supply line. Proper installation of