VOLTAGE SELECTOR SWITCH
1.Selector bar in center position, switch is open. Product is inoperative.
2.Selector bar in down position, selection is for 115 VAC.
3.Selector bar in up position, selection is for 230 VAC.
STACKING CABLE
When stacking the “I” series cuber the connecting cable (connecting the two (2) circuit boards) will allow: the bottom Unit to shut off on the full bin signal (or any error code), the top Unit will then finish the cycle it is in and shut down. The “I” series should never be stacked more than two high.
Sensor [Thermistor] Diagnosis
Sensors
Condenser or suction line – Turn Cuber power switch OFF. Disconnect sensor plug from board. Use digital multimeter set for D.C. Voltage. Turn power switch ON. Connect leads of meter across the two pins of the sen- sor being checked. Meter should read 2.5 VDC0.2 output voltage from the board. If voltage is not correct, re- place the circuit board.
Should the cuber operation indicate there may be a fault in the sensor [thermistor] or the control board cir- cuit proceed as follows.
1.Using a good multimeter, check the control board sensor output voltage.
2.If voltage checks are correct do the following:
A.Disconnect the suction line sensor (brown lead) from the control board.
B.Install the special test cord* to the control board and reinstall the sensor to the test cord terminals.
C.Connect the multimeter (set on VDC -
D.Operate the cuber in the freeze cycle.
3.As the suction line temperature decreases the
4.Sensor Shorted –
5.Sensor Open – The voltage reading will indicate the control board output voltage of 2.5 VDC.
6.Should step 4 or 5 occur during this test, the sensor will require replacement.
* Special test cord, part # 164984009, may be ordered through the Service Department.
7.Condenser Sensor (white leads) –
Complete the sensor and multimeter connections as described in 2- B, C, D
8.Shorted sensor – a steady low
9.Open sensor – the multimeter will record control board output voltage of 2.5 VDC.
10.Should sensor (thermistor) pass the voltage test proceed to the control board diagnosis for LED sequence (see page 22).
NOTE: The sensor controls the condenser fan cycling from 88/100 degree Fahrenheit. Thus any de- fects in the condenser circuit will effect the fan cycling rate.
CONDENSER FAN CYCLING CONTROL
The condenser fan on
NOTE: There is no pressure control used to cycle the fan motor on intergal condensor unit.
THERMOSTATIC EXPANSION VALVES
The following suggestions for diagnosis of automatic Thermostatic Expansion Valve (TXV) are given with the understanding that the following have been checked and are correct and/or have been corrected prior to pro- ceeding.
1. The condenser and fan blade are clean and have proper operating conditions.