5.Adjusting Syrup Flow Regulator
A.For less syrup, turn the adjusting screw counterclockwise no more than 1/4 turn at a time.
B.For more syrup, turn the adjusting screw clockwise no more than 1/4 turn at a time.
6.Repeat
7.Remove syrup diversion tube assembly from dispensing valve.
8.Install dispensing valve front cover.
CLEANING DROP-IN REFRIGERATION ASSEMBLY CONDENSER COIL
(see Figure 5)
Excessive accumulation of dust, lint, and grease on the
1.Unplug Unit power cord from electrical outlet.
2.Remove hood by loosening screw on top of the hood, then lift the hood straight up off the Unit.
3.Vacuum or use a soft brush to clean the condenser coil. If available, use compressed air to blow dust and debris out of the condenser coil.
4.Clean dust and dirt from around top of the refrigeration assembly.
5.Install hood on the Unit and secure with one screw.
6.Plug Unit power cord into electrical outlet.
CHECKING ICE WATER BATH
(see Figure 5)
A “gurgle”heard from the Unit indicates water level in the water tank is low and more water should be added to the tank for maximum cooling. Before adding more water, ice water bath and ice bank should be checked for cleanliness and the water tank coils checked for excessive mineral deposit
1.Unplug Unit power cord from electrical outlet.
2.Remove Unit hood by loosening one screw on top of the hood, then lift the hood straight up off the Unit.
3.Remove plug from the
4.Using a flashlight, inspect the ice water bath and the ice bank for cleanliness. The ice water bath should be clear and the ice bank should be free of foreign particles.
5.If cleaning of the water tank is necessary, refer to CLEANING WATER TANK in this section.
6.Fill the water tank with clean water until water runs out of the overflow groove on top front of the tank into the drip tray. USE
7.Install plug in the water fill hole.
8.Install the Unit hood and secure with screw.
9.Plug Unit power cord into electrical outlet.