Wiring Instructions For A DC Power Supply

Wiring Instructions For A DC Power Supply

Your system supports up to two –(48–60) V DC power supplies (when available).

WARNING: For equipment using –(48–60) V DC power supplies, a qualified electrician must perform all connections to DC power and to safety grounds. Do not attempt connecting to DC power or installing grounds yourself. All electrical wiring must comply with applicable local or national codes and practices. Damage due to servicing that is not authorized by Dell is not covered by your warranty. Read and follow all safety instructions that came with the product.

CAUTION: Wire the unit with copper only, unless otherwise specified, use only 10 American Wire Gauge (AWG) wire rated minimum 90 ºC for source and return. Protect the –(48–60) V DC (1 wire) with a branch circuit over- current protection rated 50 A for DC with a high interrupt current rating.

CAUTION: Connect the equipment to a –(48–60) V DC supply source that is electrically isolated from the AC source (reliably grounded –(48–60) V DC SELV source). Ensure that the –(48–60) V DC source is efficiently secured to earth (ground).

NOTE: A readily accessible disconnect device that is suitably approved and rated shall be incorporated in the field wiring.

Input Requirements

Supply voltage: –(48–60) V DC

Current consumption: 32 A (maximum)

Kit Contents

Dell part number 6RYJ9 terminal block or equivalent (1)

#6-32 nut equipped with lock washer (1)

Required Tools

Wire-stripper pliers capable of removing insulation from size 10 AWG solid or stranded, insulated copper wire

NOTE: Use alpha wire part number 3080 or equivalent (65/30 stranding)

Required Wires

One UL 10 AWG, 2 m maximum (stranded) black wire [–(48–60) V DC]

One UL 10 AWG, 2 m maximum (stranded) red wire (V DC return)

One UL 10 AWG, 2 m maximum green/yellow, green with a yellow stripe, stranded wire (safety ground)

Assembling And Connecting The Safety Ground Wire

WARNING: For equipment using –(48–60) V DC power supplies, a qualified electrician must perform all connections to DC power and to safety grounds. Do not attempt connecting to DC power or installing grounds yourself. All electrical wiring must comply with applicable local or national codes and practices. Damage due to servicing that is not authorized by Dell is not covered by your warranty. Read and follow all safety instructions that came with the product.

1.Strip the insulation from the end of the green/yellow wire, exposing approximately 4.5 mm (0.175 inch) of copper wire.

2.Using a hand-crimping tool (Tyco Electronics, 58433-3 or equivalent), crimp the ring-tongue terminal (Jeeson Terminals Inc., R5-4SA or equivalent) to the green/yellow wire (safety ground wire).

91

Page 91
Image 91
Dell R720XD Wiring Instructions For A DC Power Supply, Input Requirements, Kit Contents, Required Tools, Required Wires

R720XD, R720 specifications

The Dell PowerEdge R720 and R720xd are powerful rack servers designed to deliver exceptional performance, reliability, and scalability for a wide range of data center applications. As part of Dell's 12th generation of PowerEdge servers, they come equipped with advanced features and technologies that cater to diverse workloads.

Both models are built on the Intel Xeon processor E5-2600 family, supporting dual-socket configurations. This allows for an impressive maximum memory capacity of up to 768 GB with 32 DIMM slots, enabling efficient handling of memory-intensive applications. The R720 and R720xd are designed with efficiency in mind, allowing organizations to optimize their resource utilization while maintaining high performance.

One of the most noteworthy features of the R720 and R720xd is the flexible storage options. The R720 can accommodate up to 16 2.5-inch drives, while the R720xd extends this capacity to 24 2.5-inch drives or 12 3.5-inch drives, greatly enhancing storage scalability. This flexibility is essential for businesses with growing data needs, allowing them to configure the server according to their specific requirements.

Both servers come with the iDRAC7 (Integrated Dell Remote Access Controller), which provides advanced management capabilities. iDRAC7 enables IT administrators to remotely monitor and control the server, simplifying the management of hardware functions and system updates. The optional Lifecycle Controller further streamlines server deployment and management, offering integrated systems management capabilities.

In terms of networking, the R720 and R720xd support a variety of network interface cards, including 1 GbE and 10 GbE options. This ensures that organizations can select the right networking capabilities for their specific workload and performance requirements.

Power efficiency is another significant characteristic of these servers. Equipped with Dell’s Energy Smart technologies, they can reduce power consumption and operating costs. Features like power capping and efficient fan control help achieve optimal thermal management in the data center.

In summary, the Dell PowerEdge R720 and R720xd are robust and versatile servers that offer exceptional performance for mission-critical applications. With their advanced processor support, memory capacity, flexible storage configurations, and comprehensive management features, they are well-suited for organizations looking to enhance their IT infrastructure.