Expanded Operating Temperature
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD and in the System Event Log.
< 10% of annual operating hours | 5 °C to 40 °C at 5% to 85% RH with 26 °C dew point. |
| NOTE: Outside the standard operating temperature |
| (10 °C to 35 °C), the system can operate down to 5 |
| °C or up to 40 °C for a maximum of 10% of its annual |
| operating hours. |
| For temperatures between 35 °C and 40 °C, |
| maximum allowable dry bulb temperature by 1 °C per 175 |
| m above 950 m (1 °F per 319 ft). |
< 1% of annual operating hours | |
| NOTE: Outside the standard operating temperature |
| (10 °C to 35 °C), the system can operate down to |
| °C or up to 45 °C for a maximum of 1% of its annual |
| operating hours. |
| For temperatures between 40 °C and 45 °C, |
| maximum allowable dry bulb temperature by 1 °C per 125 |
| m above 950 m (1 °F per 228 ft). |
Expanded Operating Temperature Restrictions | • Do not perform a cold startup below 5 °C. |
| |
| • The operating temperature specified is for a |
| maximum altitude of 3050 m (10,000 ft). |
| • 130 W (4 core) processor is not supported. |
| • Redundant power supplies are required. |
| • Non Dell qualified peripheral cards and/or peripheral |
| cards greater than 25 W are not supported. |
| NOTE: For PowerEdge R720, maximum 130 W |
| processor is supported in either 8 hard drive or 16 |
| hard drive chassis. |
| NOTE: The following additional restrictions apply to |
| PowerEdge R720xd. |
| • Maximum 95 W processor supported on 3.5 inch hard |
| drive chassis. |
| • Maximum 115 W processor supported on 2.5 inch |
| hard drive chassis. |
| • Only SSDs are allowed in the hard drive slots at the |
| back of the 3.5 inch hard drive chassis. |