DeviceNet Remote I/O Communication Module RTU-DNET

bit

Status value

20/1

30/1

40/1

50/1

60/1

70/1

80/1

90/1

100/1

110/1

120/1

130/1

140/1

15

0

1

 

„Status word

Explanation

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Disabling control word Enabling control word

bit

Status value

Explanation

0

0

RTU-DNET detects DI/DO extension unit.

 

 

1

RTU-DNET does not detect DI/DO extension unit.

 

 

 

 

 

0

The configurations of RTU-DNET and the extension unit connected to

 

it are consistent.

1

 

1

The configrations of RTU-DNET and the extension unit connected to it

 

 

are inconsistent.

 

 

 

 

 

2

0

No error occurs in the special module.

 

 

1

Error occurs in the special module.

 

 

 

 

3

0

The special module operates normally.

 

 

1

The special module is detected offline.

 

 

 

 

4

0

The configuration data are valid.

 

 

1

The configuration data are invalid.

 

 

 

 

5

0

RTU-DNET operates normally.

 

 

1

The power of RTU-DNET is in low voltage.

 

 

 

 

6

0

RTU-DNET operates normally.

 

 

1

RTU-DNET detects unidentifiable special module.

 

 

 

 

 

0

RTU-DNET operates normally.

7

 

 

1

More than 8 special modules connected to RTU-DNET, or the number

 

of digital I/O points exceeds 128.

 

 

8

0/1

Reserved

 

 

 

9

0/1

Reserved

10

0/1

Reserved

 

 

 

11

0/1

Reserved

 

 

 

12

0/1

Reserved

 

 

 

13

0/1

Reserved

 

 

 

DVP-PLC Application Manual

15

Page 17
Image 17