(12) Double click on RTU-DNET icon, and you will then see “RTU Setup” dialog box.

(13) Set up the parameters in RTU-DNET and confirm its I/O information.

Item

Function

Default

 

The sum of the length of the status word of RTU-DNET and

 

Input IO

the input data of the special module connected to it. The

N/A

status word of RTU-DNET occupies 2 bytes. One input

Data Length

channel of the special module occupies 2 bytes. 8 points of

 

 

 

 

the digital input are counted as 1 byte.

 

 

The sum of the length of the control word of RTU-DNET and

 

Output IO

the output data of the special module connected to it. The

 

control word of RTU-DNET occupies 2 bytes. One output

N/A

Data Length

channel of the special module occupies 2 bytes. 8 points of

 

 

 

 

the digital output are counted as 1 byte.

 

DIDO Input

The digital input points shall be 8’s multiple. The number will

N/A

be regarded as 8 when it is less than 8 and regarded as 16

Points (X)

when it is bigger than 8 but less than 16.

 

 

 

DIDO Output

The digital output points shall be 8’s multiple. The number

 

will be regarded as 8 when it is less than 8 and regarded as

N/A

Points (Y)

16 when it is bigger than 8 but less than 16.

 

 

 

AIAO Module

The number of special modules connected to RTU-DNET.

N/A

Number

Range: 0 ~ 8

 

Diagnostic

The interval when RTU-DNET executes diagnosis.

5 (sec)

Intervel Time

Range: 1~ 65 secs

 

IO Module

How RTU-DNET will react when the special module

Alarm

connected to it is offline. You can choose “Ignored”, "Alarm”

Offine Treatment

or “stop DeviceNet IO".

 

 

 