Delta Electronics manual Byte RTU-DNET → DeviceNet master Master

Models: RTU-DNET

1 41
Download 41 pages 58.88 Kb
Page 19
Image 19

DeviceNet Remote I/O Communication Module RTU-DNET

 

Master

 

RTU-DNET

 

(byte)

 

 

 

 

 

 

 

 

 

 

z RTU-DNET → DeviceNet master

 

 

 

 

 

 

Master

 

RTU-DNET

 

(byte)

 

 

 

 

 

0

RTU-DNET

Low byte of status word of RTU-DNET

 

 

 

 

1

High byte of status word of RTU-DNET

 

 

 

 

 

 

 

2

 

Low byte of the 1st special module output channel 1

 

3

 

High byte of the 1st special module output channel 1

 

4

Special module

Low byte of the 1st special module output channel 2

 

5

 

High byte of the 1st special module output channel 2

 

 

 

 

 

 

 

N

 

X0 ~ X7 of the 1st Slim DI/DO

 

N+1

Slim DI/DO

X0 ~ X7 of the 2nd Slim DI/DO

 

 

 

 

 

 

Note:

zIf you choose to make the control word and status word of RTU-DNET to be I/O data, the first word in the I/O data area will automatically be distributed to control word and status word.

zIn the alignment of RTU-DNET and the extension modules connected to it, the data of special modules appear prior to the data of Slim DI/DO extension units.

4.4Example

1.How to read the I/O data in the extension module connected to RTU-DNET. Assume the extension modules connected to RTU-DNET are:

TE

U- ND

RT

DV P- 80 TS

DVP-16SP

DA4 0-P VD

CT4 P0- VD

PT4 P0- VD

DVP-02DA

If the I/O data do not include control word and status word of RTU-DNET, the information of the extension module connected to RTU-DNET are as follows:

DVP-PLC Application Manual

17

Page 19
Image 19
Delta Electronics manual Byte RTU-DNET → DeviceNet master Master