Location of Termination Cap
D
E V
B L
| C |
|
| Fixed | V |
| Closed | |
|
| |
F | Openable |
|
V |
| |
| B |
|
B
Openable
B
Fixed
Closed
H
V
B
I
V J XG
AM
NN
| G |
| V |
| G |
V K X | V |
V TERMINATION CAP | X AIR SUPPLY INLET | G | GAS METER |
A
RESTRICTED AREA (TERMINATION PROHIBITED)
A= clearance above grade, veranda, porch, deck, or balcony [*12 inches (30.5mc) minimum]
B= clearance to window or door that may be opened
[12 inches (30.5cm) minimum]
C = clearance to permanently closed window [minimum 12 inches (30.5cm) recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (61cm) from the
E= clearance to unventilated soffit [12 inches (30.5cm) minimum]
F= clearance to outside corner (see below)
G= clearance to inside corner (see below)
H= *not to be installed above a meter/regulator assembly within
36 inches (91.4cm) horizontally from the
I= clearance to service regulator vent outlet [*72 inches (182.9cm) minimum]
J= clearance to
K= clearance to a mechanical air supply inlet [*72 inches (182.9cm) minimum]
L= † clearance above paved
M= clearance under veranda, porch, deck [*12 inches (30.5cm) minimum ‡]
N= clearance above a roof shall extend a minimum of 24 inches (61cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 inches (45.7cm)
† vent shall not terminate directly above a
‡only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
A
V
Outside Corner | Recessed Location |
|
| D |
|
| C | C |
A = 6" (15.2cm) |
| E |
|
| |
V | V |
|
B | B = 6" (15.2cm) |
|
Balcony with No Side Wall
G |
V |
G = 12" (30.5cm) minimum clearance
Balcony with Perpendicular Side Wall
H
V
J
Combustible &
Noncombustible
H = 24" (61cm)
J = 20" (50.8cm)
C = Maximum depth of 48" (121.9cm) for recessed location
D = Minimum width for back wall of recessed location - Combustible - 38" (965mm) Noncombustible - 24" (61cm)
E = Clearance from corner in recessed location- Combustible - 6" (15.2cm) Noncombustible - 2" (5.1cm)