
SYSTEM RACK
PTM Switch Settings
Verify the switch settings of the Power Termination Module (PTM) are as follows:
S5, S7 section 1 closed; sections 2,3,4,5,6,7,8 open
S6, S8 sections 1,2,6 closed; sections 3,4,5,7,8 open
Call Processor Connection To Switch
Verify the Call Processor connection to the System rack as follows:
1.NetIDB Connection: Use the 20’
2.NetCSB Connection: Use the 20’
3.Install a Power Termination Module in the first slot on the left side of each shelf.
4.Install the NetNIM in Shelf 1, Slot 0.
5.Turn "On" both Power Supplies, turn "On" the Call Processor and note that the four LEDs on each PTM card are "On".
a.Verify that the Call Processor comes up in the Switch mode.
b.Verify that the Call Processor displays the Net- NIM’s clock status, "A Pass B Pass" in the Call Processor’s Device Activity window. If neces- sary, press the reset button S1on the NetNim to activate the clock status.)
PCM Bank Verification
PCM Bank Verification requires two Channel Interface Modules (CIMs).
1.On both CIMs place a patch cord from the top jack of J1 to the top jack of J2 (see Figure
2.Close S1, sections
3.On both CIMs set switch sections as follows:
Switch Section
S3
S4
S5
4.Set one module for System Test "5"
5.Set the second module for System Test "6".
6.Loop Primary Tx PCM to the Primary Rx PCM by connecting a cable
7.The modules display an "A" if the PCM bank is good. Press S2 to reset the module if "A" is not displayed.
•A failure on the primary displays a "1" on one or both modules.
•A failure on the secondary displays a "2" on one or both modules.
8.Repeat this procedure by moving the module on Shelf 4 to Shelf 3. Reset both modules if “A” is not displayed.
9.Repeat this procedure by moving the module on Shelf 3 to Shelf 2. Reset both modules if "A" is not displayed.
10.After the PCM bank has proven good, force failures on both the primary and secondary as follows:
Primary
•Remove cables on Shelf 1, J5 and J6.
•A "1" on both modules indicates a Primary failure.
•Reconnect the cables.
Secondary
•Remove cables on Shelf 1, J23 and J24.
•A "2" on both modules indicates a Secondary failure.
•Reconnect the cables.
•Remove the cable from Shelf 1, J3 to J4.