Rosemount 4500

Reference Manual

00809-0100-4027, Rev AA December 2005

INSTALLATION

PROCEDURES

Mount the Transmitter

For dimensional drawing information refer to Appendix A: Reference Data.

Electronics Housing

Provide 0.75 inches (19 mm) of clearance for units without an LCD display. Three inches of clearance is required for cover removal if a meter is installed.

Cover Installation

Always ensure a proper seal by installing the electronics housing cover so the o-ring is engaged. Use Rosemount O-rings.

The Rosemount 4500 is designed to be mounted directly to a process pipe or vessel using a standard sanitary fitting. The transmitter is available with either a 1.5 or 2-inch Tri-Clamp®connection or a fractional line fitting.

When installing the transmitter to the sanitary fitting it is important to use the proper sanitary clamp and gasket (user-supplied). Check the clamp and gasket specifications before installing. Refer to Table 2-2for a list of standard sanitary clamps, their respective maximum pressure ranges, and the recommended torque to be applied when mounting.

Figure 2-3. Rosemount 4500

Mounting Configuration Using a

Sanitary Fitting

1.5 or 2-in. Tri-Clamp Connection

DETAIL OF SANITARY

CONNECTION

B

A

User

Supplied

Gasket and

Clamp

4500_04_AA.EPS, 4500_24_AA.EPS

Table 2-1. Connection Size

Description

Connection Size in (mm)

A

B

 

 

 

 

11/2 inch Tri-Clamp

1.50 (38)

1.99 (50)

1.71 (43)

2 inch Tri-Clamp

2.00 (51)

2.52 (64)

2.22 (56)

Fractional Line Fitting

1.50 (38)

1.99 (50)

1.50 (38)

Table 2-2. Standard Sanitary Clamp Models

Clamp Model

13MHHM 1.5-inch 13 MHHM 2-inch

13MHHS 1.5-inch 13 MHHS 2-inch 13 MHP 1.5-inch 13 MHP 2-inch

psi @ 70 °F

(kPa @ 21 °C)

450 (3 103)

500 (3 448)

600 (4 138)

550 (3 793)

1500 (10 345)

1000 (6 896)

psi @ 250 °F

(kPa @ 121 °C)

250 (1 724)

250 (1 724)

300 (2 069)

275 (1 896)

1200 (8 276)

800 (5 517)

Recommended Torque

25in-lb (2.8 N•m)

25in-lb (2.8 N•m)

25in-lb (2.8 N•m)

25in-lb (2.8 N•m)

20 ft-lb (27 N•m)

20 ft-lb (27 N•m)

2-4

Page 12
Image 12
Emerson 4500 manual Installation Procedures, Mount the Transmitter