Emerson 4500 Advanced Functions for Hart Protocol, Saving, Recalling, Cloning Configuration Data

Models: 4500

1 70
Download 70 pages 45.62 Kb
Page 36
Image 36

Rosemount 4500

Reference Manual

00809-0100-4027, Rev AA December 2005

AMS

Right click on the device and select “Diagnostics and Test,” then “Loop test” from the menu.

1.Click Next after setting the control loop to manual.

2.Select desired analog output level. Click Next.

3.Click Next to acknowledge output being set to desired level.

4.Check the reference meter installed in the test loop to verify that it displays the commanded output value.

a.If the values match, the transmitter and the loop are configured and functioning properly.

b.If the values do not match, the current meter may be attached to the wrong loop there may be a fault in the wiring, the transmitter may require an output trim, or the reference meter may be malfunctioning.

After completing the test procedure, the display returns to the loop test screen to choose another output value or to end loop testing.

5.Select End and click Next to end loop testing.

6.Select Next to acknowledge the loop can be returned to automatic control.

7.Select Finish to acknowledge the method is complete.

ADVANCED FUNCTIONS FOR HART PROTOCOL

Saving, Recalling, and

Cloning Configuration

Data

Fast Keys

left arrow, 1, 2

 

 

Use the cloning feature of the HART Communicator or the AMS “User Configuration” feature to configure several 4500 transmitters similarly. Cloning involves configuring a transmitter, saving the configuration data, then sending a copy of the data to a separate transmitter. Several possible procedures exist when saving, recalling, and cloning configuration data. For complete instructions refer to the HART Communicator manual (publication no.

00809-0100-4276) or AMS on-line guides. One common method is as follows:

HART Communicator

1.Completely configure the first transmitter.

2.Save the configuration data:

a.Select F2 SAVE from the HART Communicator HOME/ONLINE screen.

b.Ensure that the location to which the data will be saved is set to MODULE. If it is not, select 1: Location to set the save location to

MODULE.

c.Select 2: Name, to name the configuration data. The default is the transmitter tag number.

d.Ensure that the data type is set to STANDARD. If the data type is NOT STANDARD, select 3: “Data Type”, to set the data type to

STANDARD.

e.Select F2 SAVE.

3.Connect and power the receiving transmitter and HART Communicator.

3-20

Page 36
Image 36
Emerson 4500 manual Advanced Functions for Hart Protocol, Saving, Recalling, Cloning Configuration Data