Emerson 4500 manual Re-mapping

Models: 4500

1 70
Download 70 pages 45.62 Kb
Page 33
Image 33

Reference Manual

00809-0100-4027, Rev AA December 2005

Rosemount 4500

AMS

Re-mapping

Fast Keys

1, 4, 3, 6, 4

 

 

Right click on the device and select “Device Configuration” then select “SV Config” from the menu.

1.Click Next after setting the control loop to manual.

2.Enter desired scaled variable units in “Enter SV units” box and click Next.

3.Select scaled data option: Linear and click Next.

4.Enter pressure value position 1 and click Next.

5.Enter scaled variable position 1 and click Next.

6.Enter pressure value position 2 and click Next.

7.Enter scaled variable position 2 and click Next.

8.Enter linear offset and click Next. Skip to Step 12.

9.Select Next to acknowledge that “Pressure and Scaled Variable values for position 0 set to 0.”

10.Enter pressure value position 1 and click Next.

11.Enter scaled variable position 1 and click Next.

12.Select Next to acknowledge that the loop can be returned to automatic control.

13.Select Finish to acknowledge the method is complete.

The re-mapping function allows the transmitter primary, secondary, and tertiary variables to be configured as desired. Default configuration for transmitter variables is as shown below:

Primary variable = Pressure

Secondary variable = Temperature

Tertiary variable = Scaled Variable

NOTE

The variable assigned as the primary variable drives the 4-20 mA analog output.

The scaled variable can be remapped as the primary variable if desired.

HART Communicator

From the HOME screen, enter the fast key sequence for “Re-mapping.”

1.Select OK after the control loop is set to manual (see “Setting the Loop to Manual” on page 3-2).

2.Choose desired primary variable and select Enter.

3.Choose desired secondary variable and select Enter.

4.Select OK to acknowledge the tertiary variable setting.

5.Select OK to acknowledge that the loop can be returned to automatic control.

3-17

Page 33
Image 33
Emerson 4500 manual Re-mapping