Range and Sensor Limits

Rosemount 4500 Sanitary Pressure Transmitter Range Limits

Units

psi

kPa

bar

kg/cm2

Range 1 AP

Range 1 GP

Range 2

min.

max.

min.

max.

min.

max.

 

 

 

 

 

 

0.60

30

0.6

30

10

150

4.14

206.8

4.136

206.8

68.94

1034

0.041

2.068

0.04136

2.068

0.689

10.34

0.042

2.109

0.04218

2.109

0.703

10.54

 

 

 

 

 

 

Functional Specifications

Dynamic Performance

250 milliseconds (response time + dead time)

Ambient Temperature Effect per 50°F (28°C)

±0.2% CS ± 0.02% URL

Process Temperature Effect per 104°F (58°C)

±0.3% CS + 0.03% URL

Service

Liquid, gas, vapor, and steam applications

4–20 mA (output code A)

Zero and Span Adjustment

Zero and span values can be set anywhere within the range. Span must be greater than or equal to the minimum span.

Output

Digital process variable superimposed on 4–20 mA signal, available to any host that conforms to the HART protocol.

Power Supply

External power supply required. Standard transmitter (4–20 mA) operates on 11.25 to 42.4 V dc with no load.

Load Limitations

Maximum loop resistance is determined by the voltage level of the external power supply, as described by:

Max. Loop Resistance = 43.5 (Power Supply Voltage – 11.25)

(Ohms)

1355

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

Load

500

 

 

 

 

Operating

 

 

 

 

0

 

 

 

 

 

 

 

 

Region

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11.25

20

30

42.4

Voltage (V dc)

Communication requires a minimum

loop resistance of 250 ohms.