Table 5-1. Rosemount 4500 troubleshooting table

Symptom

Corrective Actions

 

 

Transmitter milliamp reading is zero

Verify power is applied to signal terminals

 

Check power wires for reversed polarity

 

Verify terminal voltage is 11.25 to 30 V dc

 

Check for open diode across test terminal

 

 

Transmitter Not Communicating with

Verify the output is between 4 and 20 mA or saturation levels

HART Communicator

Verify clean DC Power to transmitter (Max AC noise 0.2 volts peak to peak)

 

 

Check loop resistance, 250 Ω minimum (PS voltage -transmitter voltage/loop current)

 

Check if unit is addressed properly

 

 

Transmitter milliamp reading is low or high

Verify applied pressure

 

Verify 4 and 20 mA range points

 

Verify output is not in alarm condition

 

Verify if 4 – 20 mA output trim is required

 

 

Transmitter will not respond to changes in

Check test equipment

applied pressure

Verify applied pressure is between the 4 and 20 mA set points

 

 

Verify output is not in alarm condition

 

Verify transmitter is not in Loop Test mode

 

 

Digital Pressure Variable reading is low or high

Check test equipment (verify accuracy)

 

Verify transmitter is calibrated properly

 

Verify pressure calculations for application

 

 

Digital Pressure Variable reading is erratic

Check application for faulty equipment in pressure line

 

Verify transmitter is not reacting directly to equipment turning on/off

 

Verify damping is set properly for application

 

 

Milliamp reading is erratic

Verify power source to transmitter has adequate voltage and current

 

Check for external electrical interference

 

Verify transmitter is properly grounded

 

Verify shield for twisted pair is only grounded at one end

 

 