Rosemount 4500

Figure 4-1also identifies the approximate transmitter location for each calibration task. Data flows from left to right, and a parameter change affects all values to the right of the changed parameter.

Not all calibration procedures should be performed for each 4500 transmitter. Some procedures are appropriate for bench calibration, but should not be performed during field calibration. Table 4-1identifies the recommended calibration procedures for bench or field calibration.

Figure 4-1. Transmitter Data

Flow with Calibration Options

Transmitter Ranged 0 to 100 inH2O (0 to 0,25 bar)

A/D MICRO D/A

100 in. H20

20.00 mA

4500:LT-8793

 

Online

 

1

Device setup

2

PV

100.00 in.H20

3

AO

20.00 mA

4

LRV

0.00 in.H20

5

URV

100.00 in.H20

 

SAVE

 

NOTE

Value on PV line should equal the input pressure.

Value on AO line should equal the output device reading.

CALIBRATION

4-3