Rosemount 4500

Reference Manual

00809-0100-4027, Rev AA December 2005

Alarm Level Verification

Process Alerts

Fast Keys

1, 4, 3, 5

 

 

If the transmitter electronics board, Transmitter, or LCD display is repaired or replaced, verify the transmitter alarm level before returning the transmitter to service. This feature is also useful in testing the reaction of the control system to a transmitter in an alarm state. To verify the transmitter alarm values, perform a loop test and set the transmitter output to the alarm value (see Tables 3-1and 3-2on page 3-12,and “Loop Test” on page 3-19).

Process alerts allow the user to configure the transmitter to output a HART message when the configured data point is exceeded. Process alerts can be set for pressure, temperature, or both. A process alert will be transmitted continuously if the pressure or temperature set points are exceeded and the alert mode is ON. An alert will be displayed on a HART Communicator, AMS status screen or in the error section of the LCD display. The alert will reset once the value returns within range.

NOTE

HI alert value must be higher than the LO alert value. Both alert values must be within the pressure or temperature sensor limits.

HART Communicator

To configure the process alerts with a HART Communicator, perform the following procedure:

1.From the HOME screen, follow the fast key sequence for “Process Alerts.”

2.Select 3, “Config Press Alert” to configure the pressure alert. Select 4, “Config Temp Alert” to configure the temperature alerts.

3.Use the right arrow key to configure the HI and LO alert values.

4.Use the left arrow to move back to the process alert menu. Select 1, “Press Alert Mode” to turn on the pressure alert mode. Select 2, “Temp Alert Mode” to turn on the temperature alert mode.

AMS

Right click on the device and select “Configuration Properties” from the menu.

1.In the “Analog Output” tab, locate the “Configuration Pressure Alerts” box, enter “Press Hi Alert Val” and “Press Lo Alert Val” to configure the pressure alerts.

2.Configure “Press Alert Mode” to “ON” or “OFF” using the drop down menu.

3.In the “Configuration Temperature Alerts” box, enter “Temp Hi Alert Val” and “Temp Lo Alert Val” to configure the temperature alerts.

4.Configure “Temp Alert Mode” to “ON” or “OFF” using the drop down menu and click Apply.

5.An “Apply Parameter Modification” screen appears, enter desired information and click OK.

6.After carefully reading the warning provided, select OK.