Table 18 Electrical data—Quiet-Line models (95°F/35°C) 60Hz

 

Nominal

 

 

Input Voltage-Phase

 

 

Capacity

* Electrical

 

 

 

 

 

 

 

 

 

 

 

Model #

Tons

Characteristic

208/230-1

 

208/230-3

460-3

575-3

 

 

 

 

 

 

 

 

 

 

FLA

13.0

 

 

 

 

 

 

 

 

 

27

2

WSA

16.0

 

 

 

 

 

 

 

 

 

 

 

OPD

25

 

 

 

 

 

 

 

 

 

 

 

FLA

18.8

 

12.3

6.4

5.2

 

 

 

 

 

 

 

 

37

3

WSA

23.3

 

15.2

7.8

6.4

 

 

 

 

 

 

 

 

 

 

OPD

40

 

25

15

15

 

 

 

 

 

 

 

 

 

 

FLA

 

14.8

6.9

5.9

 

 

 

 

 

 

 

 

42

3.5

WSA

 

18.3

8.5

7.3

 

 

 

 

 

 

 

 

 

 

OPD

 

30

15

15

 

 

 

 

 

 

 

 

 

 

FLA

 

21.1

10.9

8.8

 

 

 

 

 

 

 

 

67

5

WSA

 

25.9

13.4

10.8

 

 

 

 

 

 

 

 

 

 

OPD

 

45

20

15

 

 

 

 

 

 

 

 

*FLA = Full Load Amps

WSA = Wire Size Amps (minimum supply circuit current capacity) OPD = Overcurrent Protection Device (fuse or circuit breaker) Model # 14, 20 and 96 are not available in Quiet-Line versions.

Table 19 Electrical data—Standard sound and ambient models (95°F/35°C) 50Hz

 

Nominal

 

Input Voltage-Phase

 

 

Capacity

* Electrical

 

 

 

 

 

 

 

 

 

Model #

Tons

Characteristic

220-1

200/230-3

380/415-3

 

 

 

 

 

 

 

13

1

FLA

9.9

 

 

 

 

 

 

 

 

19

1.5

FLA

10.9

 

 

 

 

 

 

 

 

26

2

FLA

12.7

 

4.9

 

 

 

 

 

 

 

36

3

FLA

18.4

 

7.0

 

 

 

 

 

 

 

41

3.5

FLA

15.3

 

8.5

 

 

 

 

 

 

 

66

5

FLA

24.1

 

13.2

 

 

 

 

 

 

 

95

8

FLA

 

20.3

 

 

 

 

 

 

 

*FLA = Full Load Amps

Table 20 Electrical data—High ambient models (105°F/41°C) 50Hz

 

Nominal

 

Input Voltage-Phase

 

 

Capacity

* Electrical

 

 

 

 

 

 

 

 

 

Model #

Tons

Characteristic

220-1

200/230-3

380/415-3

 

 

 

 

 

 

 

13

1

FLA

 

 

 

 

 

 

 

 

19

1.5

FLA

 

 

 

 

 

 

 

 

26

2

FLA

14.8

 

6.0

 

 

 

 

 

 

 

36

3

FLA

20.5

 

13.1

 

 

 

 

 

 

 

41

3.5

FLA

19.8

 

9.6

 

 

 

 

 

 

 

66

5

FLA

24.2

 

13.2

 

 

 

 

 

 

 

95

8

FLA

 

 

 

 

 

 

 

 

*FLA = Full Load Amps

23