Emerson Figure i manual 2.5.6General System Charge Requirements, Evaporator Charge Levels

Models: Figure i

1 36
Download 36 pages 52.18 Kb
Page 24
Image 24
2.5.6General System Charge Requirements

Installation

2.5.6General System Charge Requirements

Liebert split system units are designed with quick-connect fittings and are factory-charged to proper levels. Due to the wide range of operating ambients and sensitivity of the system components to charge level, the system charge must be maintained at recommended levels.

If there is any doubt that the system has the correct refrigerant charge level, the correct procedure is to remove the entire system charge, evacuate the system and weigh in the recommended factory charge total for both units and any line sets or field piping.

Tables 7, 8, 11 and 12 are included for field piping allowances, condensing unit charges, line sets and evaporator charges.

Total refrigerant charge = evaporator + lines + condensing unit

NOTE

All condensing units and most evaporator units are fully charged with refrigerant. Some evaporator units are shipped from the factory with a nitrogen holding charge only. (Refer to evaporator serial tags.) If field-supplied refrigerant piping is installed, refrigerant must be added to the system. Refer to Figure 12 for field-supplied piping guidelines.

Table 12 Evaporator Charge Levels

 

Evaporator

Charge R-407C

Indoor Unit

Models

oz (kg)

 

MMD11/12E

3 (0.085)

 

 

 

 

MMD17/18E

4 (0.113)

 

 

 

Liebert

MMD23/24E

7 (0.198)

Mini-Mate2

MMD35/36E

7 (0.198)

 

 

 

 

MMD59/60E

4 (0.113)

 

 

 

 

MMD95/96E

7 (0.198) each circuit

 

 

 

 

DME020E

4 (0.113)

 

 

 

Liebert DataMate

DME027E

5 (0.141)

 

 

 

 

DME037E

6.5 (0.184)

 

 

 

Liebert Challenger

BF/BU036E

9 (0.255)

3000

BF/BU060E*

13 (0.368)

 

 

 

*Evaporator is charged with nitrogen at the factory