2.5.6General System Charge Requirements
Liebert split system units are designed with
If there is any doubt that the system has the correct refrigerant charge level, the correct procedure is to remove the entire system charge, evacuate the system and weigh in the recommended factory charge total for both units and any line sets or field piping.
Tables 7, 8, 11 and 12 are included for field piping allowances, condensing unit charges, line sets and evaporator charges.
Total refrigerant charge = evaporator + lines + condensing unit
NOTE
All condensing units and most evaporator units are fully charged with refrigerant. Some evaporator units are shipped from the factory with a nitrogen holding charge only. (Refer to evaporator serial tags.) If
Table 12 Evaporator Charge Levels
| Evaporator | Charge |
Indoor Unit | Models | oz (kg) |
| MMD11/12E | 3 (0.085) |
|
|
|
| MMD17/18E | 4 (0.113) |
|
|
|
Liebert | MMD23/24E | 7 (0.198) |
MMD35/36E | 7 (0.198) | |
|
|
|
| MMD59/60E | 4 (0.113) |
|
|
|
| MMD95/96E | 7 (0.198) each circuit |
|
|
|
| DME020E | 4 (0.113) |
|
|
|
Liebert DataMate | DME027E | 5 (0.141) |
|
|
|
| DME037E | 6.5 (0.184) |
|
|
|
Liebert Challenger | BF/BU036E | 9 (0.255) |
3000 | BF/BU060E* | 13 (0.368) |
|
|
|
*Evaporator is charged with nitrogen at the factory