3.0OPERATION

Operation

3.0OPERATION

3.1Compressor

The scroll compressor is equipped with a band type crankcase heater to resist liquid refrigerant migration into the compressor during the Off cycle. The three-phase scroll compressor requires proper phasing to ensure correct motor rotation. The component connections have been phase synchronized at the factory. Refer to 2.6 - Electrical Connections to verify proper compressor wiring.

3.2High Head Pressure

Compressor high head pressure is monitored with a pressure switch. One SPDT pressure switch is used for each compressor in the unit. If head pressure exceeds 400 psig (2760 kPa), the switch opens the compressor contactor and sends an input signal to the evaporator wall-box control. The high head pressure condition is acknowledged by pressing the alarm silence button, which will clear the alarm if the high head pressure condition no longer exists.

If the compressor is off for 1 hour, the control goes into a special cold-start mode. In the cold-start mode on a call for cooling or dehumidification, the liquid line solenoid valve (LLSV) is energized. If the high pressure switch does NOT trip within 10 seconds, the control returns to normal operation of monitoring the high head pressure switch for three occurrences in a 12-hour period. It is a rolling timer and after the third high head alarm occurs and is acknowledged by the user, it will lock off the compressor. If while in the cold-start mode the high head pressure switch DOES trip within 10 sec- onds of the activation of the LLSV, the control does not annunciate the alarm. The control will turn off the LLSV and delay 10 seconds. The control will permit this occurrence two more times, or a total of three times. If on the fourth try the high head pressure switch trips within 10 seconds, the control will annunciate the alarm, turn off the LLSV, wait for the user to acknowledge the alarm and hold the compressor off for 3 minutes, which is the normal short cycle control. The control will permit this occurrence three times. On the third occurrence, the control will lock the compressor off until the con- trol power is reset.

Check for these conditions:

Power shut off to the condensing unit

Condensing unit fan not working

Defective head pressure control valves

Closed services valves

Dirty condensing coils

Crimped lines

3.3Liebert Lee-Temp Flood Back Head Pressure Control

Outdoor condensing unit components for head pressure control include a receiver, heater and three-way head pressure control valve. The head pressure control valve operates to maintain a mini- mum condensing pressure. During low ambient temperature operation, the valve meters discharge gas into the receiver to maintain a discharge pressure operating against the valve dome. This closes the condenser port, backing liquid refrigerant into the condenser coil, reducing its area available for condensing. A receiver sized to hold the additional charge required to flood the condenser is provided.

Atemperature-compensated heater maintains the liquid refrigerant pressure during Off cycles. A liq- uid pressure switch is also installed to turn the heater Off during operation, when the receiver pres- sure is high. The heater pressure switch has a cutout of 150 PSIG (1034 kPa) and a cut-in of 100 PSIG (690 kPa). The receiver includes a pressure relief valve set for 475 PSIG (3275 kPa).