CHAPTER 1 Installation Data

1.3 Installation Specifications

1.3Installation Specifications

This section explains installation specification of each equipment.

1.3.1 Installation specifications (PRIMEQUEST 2400E)

TABLE 1.2 Installation Specifications (PRIMEQUEST 2400E)

 

 

 

 

Item

 

 

 

 

 

Contents

 

External

Width

 

 

 

 

 

 

 

 

445(17.52)

 

 

Dimensions

Length(*1)

 

 

 

 

 

 

 

 

782(30.79)

 

 

[mm(in.)]

Height

 

 

 

 

 

 

 

 

438(17.25) 10U

 

Mass [kg(lb)] (*2)

 

 

 

 

 

 

 

 

128(282)

 

 

Conditions for

Maximum Calorific value

 

Input

 

Interruptible Power

11,887(11,266)

 

Air

[kJ/h(BTU/h)]

 

 

 

Voltage:

 

Supply(*13)

 

 

 

Conditioning

 

 

 

 

 

200V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High efficiency Power

11,805(11,189)

 

 

 

 

 

 

 

 

 

 

supply(*13)

 

 

 

 

 

 

 

 

 

Input

 

Interruptible Power

12,528(11,874)

 

 

 

 

 

 

 

Voltage:

 

Supply(*13)

 

 

 

 

 

 

 

 

 

100V

 

 

 

 

 

 

 

Displacement

 

 

 

Recommended

Environmental

10(353)

 

 

 

[m3/min(ft3/min)](*3)

 

 

 

temperature

 

 

 

 

 

 

 

 

 

 

Maximum

 

 

 

24(848)

 

 

 

Temperature and

 

 

 

Operati

Temperature[ºC(ºF)]

(*5)

 

 

 

Humidity Conditions(*4)

 

ng Time

Humidity[%RH]

20 to 80

 

 

 

 

 

 

 

 

 

 

Highest Wet bulb

29(84.2)

 

 

 

 

 

 

 

 

 

 

Temperature[ºC(ºF)]

 

 

 

 

 

 

 

 

 

Down

Temperature[ºC(ºF)]

0 to 50(32 to 122)

 

 

 

 

 

 

 

Time(*6

Humidity[%RH]

8 to 80

 

 

 

 

 

 

 

 

)

 

Highest Wet bulb

29(84.2)

 

 

 

 

 

 

 

 

 

 

Temperature[ºC(ºF)]

 

 

 

 

Noise[dB](*7,*8)

 

 

 

 

 

 

 

 

60

 

 

 

Acoustic power level[B](*8)

 

 

 

 

 

7.8

 

 

 

Permissible Vibration

 

Operating Time(including waiting

4.0(400)( synthetic

 

 

[m/s2(gal)]

 

time)

 

 

 

seismic wave)

 

 

 

 

 

Down time(*9)

 

10.0(1000)( synthetic

 

 

 

 

 

 

 

 

 

 

 

 

seismic wave)

 

 

Permissible dust level[mg/m3]

 

 

 

0.15

 

 

Power

Input Voltage and Pulse number

 

 

 

200 to 240VAC±10%

 

Conditions

 

 

 

 

 

 

 

 

 

 

100 to 120VAC±10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency and Fluctuation

 

 

 

 

 

50/60 Hz+2/-4%

 

 

Maximum Power

 

Operating

Input

Interruptible

4.17 kW/4.39 kVA

 

 

Consumption

 

time

 

Voltage :

Power

 

 

 

 

/Apparent Power

 

 

 

 

 

200 V

Supply(*13)

 

 

 

 

 

 

 

 

 

 

 

 

 

High efficiency

4.04 kW/4.25 kVA

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

supply(*13)

 

 

 

 

 

 

 

 

 

 

Input

Interruptible

4.42 kW/4.65 kVA

 

 

 

 

 

 

 

 

Voltage :

Power

 

 

 

 

 

 

 

 

 

 

100 V

Supply(*13)

 

 

 

 

 

 

Standby time

 

 

 

0.079kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Factor(*10)

 

 

 

 

 

 

 

 

0.95 or more

 

 

 

 

 

 

 

 

 

 

Inrush current[A][Rush time](*11)

 

 

 

20 or less

 

 

 

Leak current[mA](*12)

 

 

 

 

 

6.8 or less

at 200V

 

 

 

 

 

 

 

 

 

 

 

 

3.5 or less

at 100V

*1: Dimensions without protrusions (Dimensions including the front cover are 832mm(32.76in)).

 

 

 