CHAPTER 1 Installation Data
1.3 Installation Specifications
1.3Installation Specifications
This section explains installation specification of each equipment.
1.3.1 Installation specifications (PRIMEQUEST 2400E)
TABLE 1.2 Installation Specifications (PRIMEQUEST 2400E)
|
|
|
| Item |
|
|
|
|
| Contents | |||
| External | Width |
|
|
|
|
|
|
|
| 445(17.52) |
| |
| Dimensions | Length(*1) |
|
|
|
|
|
|
|
| 782(30.79) |
| |
| [mm(in.)] | Height |
|
|
|
|
|
|
|
| 438(17.25) 10U | ||
| Mass [kg(lb)] (*2) |
|
|
|
|
|
|
|
| 128(282) |
| ||
| Conditions for | Maximum Calorific value |
| Input |
| Interruptible Power | 11,887(11,266) | ||||||
| Air | [kJ/h(BTU/h)] |
|
|
| Voltage: |
| Supply(*13) |
|
| |||
| Conditioning |
|
|
|
|
| 200V |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| High efficiency Power | 11,805(11,189) | ||
|
|
|
|
|
|
|
|
|
| supply(*13) |
|
| |
|
|
|
|
|
|
| Input |
| Interruptible Power | 12,528(11,874) | |||
|
|
|
|
|
|
| Voltage: |
| Supply(*13) |
|
| ||
|
|
|
|
|
|
| 100V |
|
|
|
|
| |
|
| Displacement |
|
|
| Recommended | Environmental | 10(353) |
| ||||
|
| [m3/min(ft3/min)](*3) |
|
|
| temperature |
|
|
| ||||
|
|
|
|
|
|
| Maximum |
|
|
| 24(848) |
| |
|
| Temperature and |
|
|
| Operati | Temperature[ºC(ºF)] | (*5) |
| ||||
|
| Humidity Conditions(*4) |
| ng Time | Humidity[%RH] | 20 to 80 |
| ||||||
|
|
|
|
|
|
|
|
| Highest Wet bulb | 29(84.2) |
| ||
|
|
|
|
|
|
|
|
| Temperature[ºC(ºF)] |
|
| ||
|
|
|
|
|
|
| Down | Temperature[ºC(ºF)] | 0 to 50(32 to 122) | ||||
|
|
|
|
|
|
| Time(*6 | Humidity[%RH] | 8 to 80 |
| |||
|
|
|
|
|
|
| ) |
| Highest Wet bulb | 29(84.2) |
| ||
|
|
|
|
|
|
|
|
| Temperature[ºC(ºF)] |
|
| ||
|
| Noise[dB](*7,*8) |
|
|
|
|
|
|
|
| 60 |
| |
|
| Acoustic power level[B](*8) |
|
|
|
|
| 7.8 |
| ||||
|
| Permissible Vibration |
| Operating Time(including waiting | 4.0(400)( synthetic | ||||||||
|
| [m/s2(gal)] |
| time) |
|
|
| seismic wave) | |||||
|
|
|
|
| Down time(*9) |
| 10.0(1000)( synthetic | ||||||
|
|
|
|
|
|
|
|
|
|
|
| seismic wave) | |
|
| Permissible dust level[mg/m3] |
|
|
| 0.15 |
| ||||||
| Power | Input Voltage and Pulse number |
|
|
| 200 to 240VAC±10% | |||||||
| Conditions |
|
|
|
|
|
|
|
|
|
| 100 to 120VAC±10% | |
|
|
|
|
|
|
|
|
|
|
|
| 1φ |
|
|
| Frequency and Fluctuation |
|
|
|
|
| 50/60 | |||||
|
| Maximum Power |
| Operating | Input | Interruptible | 4.17 kW/4.39 kVA | ||||||
|
| Consumption |
| time |
| Voltage : | Power |
|
| ||||
|
| /Apparent Power |
|
|
|
|
| 200 V | Supply(*13) |
|
| ||
|
|
|
|
|
|
|
|
|
|
| High efficiency | 4.04 kW/4.25 kVA | |
|
|
|
|
|
|
|
|
|
|
| Power |
|
|
|
|
|
|
|
|
|
|
|
|
| supply(*13) |
|
|
|
|
|
|
|
|
|
| Input | Interruptible | 4.42 kW/4.65 kVA | |||
|
|
|
|
|
|
|
| Voltage : | Power |
|
| ||
|
|
|
|
|
|
|
| 100 V | Supply(*13) |
|
| ||
|
|
|
| Standby time |
|
|
| 0.079kW |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Power Factor(*10) |
|
|
|
|
|
|
|
| 0.95 or more | ||
|
|
|
|
|
|
|
| ||||||
|
| Inrush current[A][Rush time](*11) |
|
|
| 20 or less |
| ||||||
|
| Leak current[mA](*12) |
|
|
|
|
| 6.8 or less | at 200V | ||||
|
|
|
|
|
|
|
|
|
|
|
| 3.5 or less | at 100V |
*1: Dimensions without protrusions (Dimensions including the front cover are 832mm(32.76in)).
|
|
|