CHAPTER 3 Notes on Carrying In and Installing the Product 3.1 Elevator Load Conditions
CHAPTER 3 Notes on Carrying In and
Installing the Product
This chapter provides notes on carrying in and installing the PRIMEQUEST 2000 series server.
3.1Elevator Load Conditions
The rack with the device mounted is wider than the average computer. Therefore, to use an elevator to carry in the rack, the rack may need the side boards or doors removed before loading on the elevator. When using an elevator to carry in the rack, see the elevator load conditions in “TABLE 3.1 Elevator load conditions” and confirm that you are properly loading the rack on the elevator.
TABLE 3.1 Elevator load conditions
|
|
| Width |
| Depth |
| Height |
| Width |
| Height |
|
| Rack |
|
|
| Load | (*1) |
| (*1) |
| (*1) |
| (*2) |
| (*2) |
|
| Models |
|
| Elevator |
|
|
|
|
|
|
|
|
|
|
| 2742/2737/2724/ |
| |
| capacity |
|
|
|
|
|
|
|
|
|
|
|
| ||
| code |
|
|
|
|
|
|
|
|
|
|
| 2642/2624/2616 |
| |
| [kg] |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| Models |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1740/1640/1624 |
|
| 450 | 1400 |
| 850 |
| 2300 |
| 800 |
| 2100 |
|
| Cannot be loaded |
| |
| 600 | 1400 |
| 1100 |
| 2300 |
| 800 |
| 2100 |
|
| Cannot be loaded |
| |
| 750 | 1400 |
| 1350 |
| 2300 |
| 800 |
| 2100 |
|
| Can be loaded |
| |
| 900 | 1600 |
| 1350 |
| 2300 |
| 900 |
| 2100 |
|
| Can be loaded |
| |
| 1000 | 1600 |
| 1500 |
| 2300 |
| 900 |
| 2100 |
|
| Can be loaded |
| |
| 1800 |
| 1300 |
|
| 1000 |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| 1150 | 1800 |
| 1500 |
| 2300 |
| 1000 |
| 2100 |
|
| Can be loaded |
| |
| 2000 |
| 1350 |
|
| 1100 |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| 1350 | 1800 |
| 1700 |
| 2300 |
| 1000 |
| 2100 |
|
| Can be loaded |
| |
| 2000 |
| 1500 |
|
| 1100 |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| 1600 | 2000 |
| 1750 |
| 2300 |
| 1100 |
| 2100 |
|
| Can be loaded |
| |
| 2150 |
| 1600 |
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
*1 Interior dimensions of the cab [mm] |
|
|
|
|
|
|
|
|
|
| |||||
*2 Door opening dimensions [mm] |
|
|
|
|
|
|
|
|
|
|
|
3.2Earthquake Preparedness Measures
The purpose of the earthquake preparedness measures is to prevent the computer from falling and breaking, and to ensure operator safety as well as quick system recovery. To prevent damage to the computer system from an earthquake, Fujitsu provides an earthquake countermeasure called "fixed construction." (A fixed construction prevents the device from falling by fixing it in place.)
The necessity of a fixed construction is determined from the following factors:
-Magnitude of floor vibrations at the installation site
-Whether the floor is a raised floor
-Device structure
Before choosing an earthquake countermeasure and performing the actual work for earthquake preparedness, consult with Fujitsu's engineering works department.
|
|
|