CHAPTER 3 Notes on Carrying In and Installing the Product 3.1 Elevator Load Conditions

CHAPTER 3 Notes on Carrying In and

Installing the Product

This chapter provides notes on carrying in and installing the PRIMEQUEST 2000 series server.

3.1Elevator Load Conditions

The rack with the device mounted is wider than the average computer. Therefore, to use an elevator to carry in the rack, the rack may need the side boards or doors removed before loading on the elevator. When using an elevator to carry in the rack, see the elevator load conditions in TABLE 3.1 Elevator load conditionsand confirm that you are properly loading the rack on the elevator.

TABLE 3.1 Elevator load conditions

 

 

 

Width

 

Depth

 

Height

 

Width

 

Height

 

 

Rack

 

 

 

Load

(*1)

 

(*1)

 

(*1)

 

(*2)

 

(*2)

 

 

Models

 

 

Elevator

 

 

 

 

 

 

 

 

 

 

 

2742/2737/2724/

 

 

capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

code

 

 

 

 

 

 

 

 

 

 

 

2642/2624/2616

 

 

[kg]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1740/1640/1624

 

 

P-6-C0

450

1400

 

850

 

2300

 

800

 

2100

 

 

Cannot be loaded

 

 

P-9-C0

600

1400

 

1100

 

2300

 

800

 

2100

 

 

Cannot be loaded

 

 

P-11-C0

750

1400

 

1350

 

2300

 

800

 

2100

 

 

Can be loaded

 

 

P-13-C0

900

1600

 

1350

 

2300

 

900

 

2100

 

 

Can be loaded

 

 

P-15-C0

1000

1600

 

1500

 

2300

 

900

 

2100

 

 

Can be loaded

 

 

1800

 

1300

 

 

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P-17-C0

1150

1800

 

1500

 

2300

 

1000

 

2100

 

 

Can be loaded

 

 

2000

 

1350

 

 

1100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P-20-C0

1350

1800

 

1700

 

2300

 

1000

 

2100

 

 

Can be loaded

 

 

2000

 

1500

 

 

1100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P-24-C0

1600

2000

 

1750

 

2300

 

1100

 

2100

 

 

Can be loaded

 

 

2150

 

1600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1 Interior dimensions of the cab [mm]

 

 

 

 

 

 

 

 

 

 

*2 Door opening dimensions [mm]

 

 

 

 

 

 

 

 

 

 

 

3.2Earthquake Preparedness Measures

The purpose of the earthquake preparedness measures is to prevent the computer from falling and breaking, and to ensure operator safety as well as quick system recovery. To prevent damage to the computer system from an earthquake, Fujitsu provides an earthquake countermeasure called "fixed construction." (A fixed construction prevents the device from falling by fixing it in place.)

The necessity of a fixed construction is determined from the following factors:

-Magnitude of floor vibrations at the installation site

-Whether the floor is a raised floor

-Device structure

Before choosing an earthquake countermeasure and performing the actual work for earthquake preparedness, consult with Fujitsu's engineering works department.

 

 

 